Skip to main content

E4 Help Desk

CANopen Service Data Objects

CANopen - Service Data Objects (SDO)

All user adjustable parameters are accessible through the CAN communication interface using Service Data Objects (SDO)

The operation of SDOs is on the basis of client/server relationship. The client sends requests and the server responds to those requests.

SDO Functions

SDO message may be used for the following functions:

  • Read a parameter value

  • Write to a parameter

SDO COB-ID

By default, SDO messages have the following COB-ID's:

  • Client to server message has the COB-ID 600h + node ID

  • Server to client response will have the COB-ID 580h + node ID

The node ID is the value set in Parameter P-68.0.

SDO Message Format

SDO messages have the following format:

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Control Byte

Object Address (16 Bit)

Sub Index (8 Bit)

Data (Up to 32 Bits)

LSB

MSB

SDO Control Byte

The following values for the SDO Control Byte are supported:

Control Byte

Function

0x40

Read Request (Any Size Data)

0x4F

Read Request - Single Byte

0x4B

Read Request - Single Word

0x43

Read Request - Double Word

0x2F

Write Request - Single Byte

0x2B

Write Request - Single Word

0x23

Write Request - Double Word

0x60

Write Response - Successful

0x80

Write Response - Unsuccessful