P-36 Modbus Parameters
Modbus Parameters
Par. | Description | Minimum | Maximum | Default | Units | Access | Change During Run | Available Motor Modes | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus-RTU Register | Modbus-RTU Register - Legacy | Modbus-TCP Register | Ethernet IP Register | Ethercat Register | BACnet MS/TP Register | Profinet Register | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P-36.0 | Modbus RTU Address | 0 | 247 | 1 | - | RW | - | - | - | - | 2088 | 0 | 136 | - | - | - | - | - | - | |
P-36.1 | Modbus RTU Baud Rate | 0 | 4 | 115200 | - | RW | - | - | - | - | 2088 | 1 | 11361 | - | - | - | - | - | - | |
| ||||||||||||||||||||
P-36.2 | Modbus RTU Data Format | 0 | 3 | n-1 | - | RW | - | - | - | - | 2088 | 2 | 11362 | - | - | - | - | - | - | |
| ||||||||||||||||||||
P-36.3 | Modbus RTU Comms Loss Detection | 0 | 1 | 0 | - | RW | - | - | - | - | 2088 | 3 | 11363 | - | - | - | - | - | - | |
| ||||||||||||||||||||
P-36.4 | Modbus RTU Comms Loss Timeout | 0.0 | 5. | 1.0 | s | RW | - | - | - | - | 2088 | 4 | 11364 | - | - | - | - | - | - | |
If a valid telegram is not received by the drive within this time period, the drive will assume a loss of communications has occurred and react according to P-36.5. Setting to 0 will disable the timeout, however this is not recommended. | ||||||||||||||||||||
P-36.5 | Modbus RTU Comms Loss Action | 0 | 3 | trip | - | RW | - | - | - | - | 2088 | 5 | 11365 | - | - | - | - | - | - | |
| ||||||||||||||||||||