P-58 DA3 Analog Input 2 Setup
Par. | Description | Minimum | Maximum | Default | Units | Access | Change During Run | Available Motor Modes | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus-RTU Register | Modbus-RTU Register - Legacy | Modbus-TCP Register | Ethernet IP Register | Ethercat Register | BACnet MS/TP Register | Profinet Register |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P-58.0 | DA3 Minimum V / mA | 0.0 | 20.0 | 0.0 | V/mA | RW | - | - | - | - | 209E | 0 | 158 | - | - | - | - | - | - |
P-58.1 | DA3 Maximum V / mA | 0.0 | 20.0 | 10.0 | V/mA | RW | - | - | - | - | 209E | 1 | 11581 | - | - | - | - | - | - |
P-58.2 | DA3 Minimum Speed | -P-01 | P-01 | 0.00 | Hz/RPM | RW | - | - | - | - | 209E | 2 | 11582 | - | - | - | - | - | - |
P-58.3 | DA3 Maximum Speed | -P-01 | P-01 | 50.00 | Hz/RPM | RW | - | - | - | - | 209E | 3 | 11583 | - | - | - | - | - | - |
P-46.2 and P-46.3 are used together to define the connected sensor range for PI operation, so that all PI related parameters can be set in Engineering units. Example : If you have a sensor that measures 2‑10 bar. Enter 2.0 in P‑46.2 and 10.0 in P46.3. | |||||||||||||||||||