P-01..P-11 Basic Parameters
Basic Parameters
Par. | Description | Minimum | Maximum | Default | Units | Access | Change During Run | Available Motor Modes | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus-RTU Register | Modbus-RTU Register - Legacy | Modbus-TCP Register | Ethernet IP Register | Ethercat Register | BACnet MS/TP Register | Profinet Register |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P-01 | Maximum Frequency / Speed Limit | P-02 | 500.0 | 50.0 (60.0) | Hz/RPM | RW | - | - | - | - | 2065 | 0 | 101 | - | - | - | - | - | - |
P-02 | Minimum Frequency / Speed Limit | 0.00 | P-01 | 0.00 | Hz/RPM | RW | - | - | - | - | 2066 | 0 | 102 | - | - | - | - | - | - |
P-03.0 | Acceleration Ramp Time | 0.00 | 600.0 | 5.00 | s | RW | - | - | - | - | 2067 | 0 | 103 | - | - | - | - | - | - |
Time taken for the motor speed to increase from 0 to Motor Rated Frequency (P-09). | |||||||||||||||||||
P-03.1 | Acceleration Ramp Time 2 | 0.00 | 600.0 | 2.00 | s | RW | - | - | - | - | 2067 | 1 | 11031 | - | - | - | - | - | - |
P-03.2 | Acceleration Ramp Switchover Speed | 0.00 | P-09 | 0.00 | Hz/RPM | RW | - | - | - | - | 2067 | 2 | 11032 | - | - | - | - | - | - |
Speed at which the drive switches from Acceleration Ramp Time (P-03.0) to Acceleration Ramp Time 2 (P-03.1). | |||||||||||||||||||
P-04.0 | Deceleration Ramp Time | 0.00 | 600.0 | 5.00 | s | RW | - | - | - | - | 2068 | 0 | 104 | - | - | - | - | - | - |
If set to 0.00 motor will coast to stop. | |||||||||||||||||||
P-04.1 | Deceleration Ramp Time on Stop Command | 0.00 | 600.0 | 0.00 | s | RW | - | - | - | - | 2068 | 1 | 11041 | - | - | - | - | - | - |
If set to 0.00 then P-04.0 is used. | |||||||||||||||||||
P-05.0 | Terminal & Keypad Stop Mode | 0 | 3 | 0 | - | RW | - | - | - | - | 2069 | 0 | 105 | - | - | - | - | - | - |
Selects how the drive stops the motor following a stop command. 0 : Ramp to stop (P-04.x) 1 : Coast to stop 2 : Ramp to stop (P-04.x) with AC Flux braking 3 : Ramp to minimum speed (P-04.0) and then Coast | |||||||||||||||||||
P-05.1 | Mains Loss Reaction | 0 | 3 | rP | - | RW | - | - | - | - | 2069 | 1 | 11051 | - | - | - | - | - | - |
Determines the drive response when the mains supply is lost. | |||||||||||||||||||
0 (rP) : Ramp to stop (P-04.x) 1 (coASt) : Coast to Stop 2 (F-rP) : Fast Ramp (P-24) to stop 3 (triP) : No action drive trips mains loss (InLoSS) | |||||||||||||||||||
P-05.2 | DC Supply Enable | 0 | 1 | 0 | - | RW | - | - | - | - | 2069 | 2 | 11052 | - | - | - | - | - | - |
Enables operation from DC power supply source connected to power terminals +DC/-DC. | |||||||||||||||||||
0: Disabled 1: Enabled | |||||||||||||||||||
P-06 | Energy Optimiser | 0 | 1 | 0 | - | RW | - | - | - | - | 206A | 0 | 106 | - | - | - | - | - | - |
0: Disable 1: Enable | |||||||||||||||||||
P-07 | Motor Rated Voltage/Back EMF | 0 | 250 / 500 | 230 / 400 | V | RW | - | - | - | - | 206B | 0 | 107 | - | - | - | - | - | - |
Motor Rated Voltage (Induction Motor)/ Back EMF at rated speed (Synchronous Motors). | |||||||||||||||||||
P-08 | Motor Rated Current | Rating Dependent | Rating Dependent | Rating Dependent | A | RW | - | - | - | - | 206C | 0 | 108 | - | - | - | - | - | - |
P-09 | Motor Rated Frequency | 5 | 500 | 50 (60) | Hz | RW | - | - | - | - | 206D | 0 | 109 | - | - | - | - | - | - |
P-10.0 | Motor Rated Speed | 0 | 30000 | 0 | RPM | RW | - | - | - | - | 206E | 0 | 110 | - | - | - | - | - | - |
Entering motor nameplate value enables the slip compensation function when operating in V/F Mode (P-51.1 = 1). NOTE: If P-09 value is changed, P-10 value is reset to 0. | |||||||||||||||||||
P-10.1 | Operating Units | 0 | 1 | 0 | Hz/RPM | RW | - | - | - | - | 206E | 1 | 11101 | - | - | - | - | - | - |
0: Hz 1: RPM (P-10.0 must also have been populated) | |||||||||||||||||||
P-11.0 | Boost Voltage | 0.0 | Rating Dependent | Drive Dependent | % | RW | - | - | - | - | 206F | 0 | 111 | - | - | - | - | - | - |
Applies additional voltage at low speeds to improve motor torque for Induction Motors operating in V/F mode (P51.1 = 1). If set to 0.0 the drive will automatically calculate the required Boost Voltage. | |||||||||||||||||||
P-11.1 | Torque Boost Current at Start (PM Motors) | 0.0 | Rating Dependent | 10.0 | % | RW | - | - | - | - | 206F | 1 | 11111 | - | - | - | - | - | - |
P-11.2 | Torque Boost Current at Start Frequency Limit (PM Motors) | 0.0 | Rating Dependent | 10.0 | % | RW | - | - | - | - | 206F | 2 | 11112 | - | - | - | - | - | - |
P-11.3 | Torque Boost Current at Stop (PM Motors) | 0.0 | Rating Dependent | 10.0 | % | RW | - | - | - | - | 206F | 3 | 11113 | - | - | - | - | - | - |
P-11.4 | Torque Boost Current Frequency Limit at Stop (PM Motors) | 0.0 | Rating Dependent | 10.0 | % | RW | - | - | - | - | 206F | 4 | 11114 | - | - | - | - | - | - |