P-12..P-14 Control Source, References & Application Modes

Control Source, References & Application Modes

Par.

Description

Minimum

Maximum

Default

Units

Access

Change During Run

Available Motor Modes

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus-RTU Register

Modbus-RTU Register - Legacy

Modbus-TCP Register

Ethernet IP Register

Ethercat Register

BACnet MS/TP Register

Profinet Register

P-12.0

Control Source

0

8

tEr

-

RW

-

-

-

-

2070

0

112

-

-

-

-

-

-

If set to 0.0 the drive will automatically calculate the required Boost Voltage.

0 (tEr): Terminal only

1 (PAd-1): Keypad Only - Uni-Directional

2 (Pad-2): Keypad Only - Bi-Directional

3 (nEt): Communications network using Internal ramps (P-04.x)

4 (nEt-r): Communications network using network ramps

5 (Pi): PI Mode

6 (PiAS): PI Analog Summation

7 (FoL): Master Follower Mode

8 (OtP): Optitools-Pro Control

P-12.1

Primary Reference Source

0

10

AI1

-

RW

-

-

-

-

2070

1

11121

-

-

-

-

-

-

Selects the primary source of the speed reference signal, the value is pre-set based on the setting of P-15 Terminal Macros, page.Terminal Macros

0 (AI1): Terminal DA4 Analog Input 1

1 (PAd): Keypad/MOP

2 (Pi): PI Controller

3 (AI2): Terminal DA3 Analog Input 2

4 (nEt): Communications network

5 (P-01): Parameter P-01

6 (Pr1): Preset Speed 1 (P-20)

7 (Pr2): Preset Speed 2 (P-21)

8 (Pr3): Preset Speed 3 (P-22)

9 (Pr4): Preset Speed 4 (P-23)

10 (FoL): Master Follower Mode

P-12.2

Secondary Reference Source

0

10

Pr1

-

RW

-

-

-

-

2070

2

11122

-

-

-

-

-

-

Selects the Secondary source of the speed reference signal, the value is pre-set based on the setting of P-15 Terminal Macros, page.Terminal Macros

0 (AI1): Terminal DA4 Analog Input 1

1 (PAd): Keypad/MOP

2 (Pi): PI Controller

3 (AI2): Terminal DA3 Analog Input 2

4 (nEt): Communications network

5 (P-01): Parameter P-01

6 (Pr1): Preset Speed 1 (P-20)

7 (Pr2): Preset Speed 2 (P-21)

8 (Pr3): Preset Speed 3 (P-22)

9 (Pr4): Preset Speed 4 (P-23)

10 (FoL): Master Follower Mode

P-12.3

Communications Source

0

3

rtU

-

RW

-

-

-

-

2070

3

11123

-

-

-

-

-

-

If set to 0.0 the drive will automatically calculate the required Boost Voltage.

0 (rtU): Modbus RTU

1 (CAn): CANopen

2 (FbUS): Fieldbus Option Module if inserted

P-12.4

Keypad Mode Command Source

0

2

0

-

RW

-

-

-

-

2070

4

11124

-

-

-

-

-

-

If set to 0.0 the drive will automatically calculate the required Boost Voltage.

0: Keypad Buttons Only

1: Keypad Buttons plus Digital Input needs to be active

2: Digital Input Only

P-13

Application Mode

0

2

0

-

RW

-

-

-

-

2071

0

113

-

-

-

-

-

-

Provides a quick set up to configure key parameters according to the intended application of the drive. Parameters are preset according to the table.

NOTE:- For a PTC thermistor set Ptc-th or for a KTY thermistor set ty-th.

Setting

Application

Current Limit (P-54.0)

Torque Characteristic

Spin Start (P-33.0)

Thermal Overload Limit Reaction (P-60.1)

0

General

150%

Constant

0 : Off

0: Trip

1

Pump

110%

Variable

0 : Off

1: Current Limit Reduction

2

Fan

110%

Variable

1 : On

1: Current Limit Reduction

Note

For pump and fan applications, Mode 1/2 is intended for centrifugal-type loads. For other pump or fan types, Mode 0 may be required.

P-14

Extended Group Access Code

0

9999

0

-

RW

-

-

-

-

2072

0

114

-

-

-

-

-

-

Enables access to Extended Parameter Groups. The code may be changed by the user in P-37 if desired.