P-37..P-46 Access, Display Scaling & PI Control

Access, Display Scaling & PI Control

Par.

Description

Minimum

Maximum

Default

Units

P-37

Level 2 Access Definition

0

9999

0

-

P-38

Parameter Access Lock

0

1

0

-

0: Unlocked. All parameters can be accessed and changed.

1: Locked. Parameter values can be displayed, but cannot be changed, except P-38.

P-39

Positive/Negative Logic Select

0

1

0

-

Sets whether digital inputs are positive or negative logic.

NOTE: STO inputs are always positive logic and are not affected by this parameter.

0: Positive Logic

1: Negative Logic

P-40.0

Display Scaling Source

0

4

0

-

0: Output Speed

1: Output Current

2: Analog Input 2 (DA3) Value

3: PI Feedback

4: DC Bus Voltage

P-40.1

Display Scaling Factor

0.000

30.000

0.000

-

Allows the drive to display an alternative output unit scaled from an existing parameter, e.g., to display speed in metres per second based on the output frequency.

Value taken from the data source set in Display Scaling Source (P‑40.0) is first multiplied by this value then divided by Display Scaling Divide (P‑40.2).

If you want to just divide the value, set this to 1.000 and adjust P‑40.2 accordingly.

This function is disabled if this parameter is set to 0.

P-40.2

Display Scaling Divide

1.000

100.000

1.000

-

P-41

PI Controller Proportional Gain

0.0

30.0

1.0

-

P-42

PI Controller Integral Time

0.0

30.0

1.0

s

P-43.0

PI Operation

0

1

0

-

0: Discontinuous. On disable, PI controller disabled.

1: Continuous. PI runs continually regardless of drive state.

P-43.1

PI Mode

0

1

0

-

0: Direct Operation, the motor speed will increase when the measured value from the feedback drops

1: Inverse Operation, the motor speed will decrease when the measured value from the feedback drops.

P-43.2

PI Wake Mode

0

1

0

-

0: Wake at Minimum

1: Wake at Maximum

P-44

PI Reference (Setpoint) Source Select

0

2

0

-

0: Digital Fixed Value (P-45 used)

1: Analog Input 1 (DA4)

2: Fieldbus Process Data

P-45

PI Fixed Reference

P-46.2

P-46.3

0.0

-

P-46.0

PI Feedback Source

0

5

0

-

0: Analog Input 2 (DA3)

1: Analog Input 1 (DA4)

2: Motor Load Current (% of P-08)

3: DC Bus Voltage

4: Analog Input 1 (DA4) - Analog Input 2 (DA3)

5: Maximum Value between Analog Input 1 (DA4) and Analog Input 2 (DA3)

P-46.1

PI Feedback Function

0

1

0

-

0: Direct Operation, the motor speed will increase when the measured value from the feedback drops

1: Inverse Operation, the motor speed will decrease when the measured value from the feedback drops.

P-46.2

PI Feedback Sensor Minimum Signal

-1000.0

P-46.3

0.0

-

P-46.3

PI Feedback Sensor Maximum Signal

P-46.2

1000.0

100.0

-

P-46.2 and P-46.3 are used together to define the connected sensor range for PI operation, so that all PI related parameters can be set in Engineering units.

Example : If you have a sensor that measures 2‑10 bar.

Enter 2.0 in P‑46.2 and 10.0 in P46.3.