P-35 Analog Input 1 (DA4) & Master Follower Scaling
Analog Input 1 (DA4) & Master Follower Scaling
Par. | Description | Minimum | Maximum | Default | Units | Access | Change During Run | Available Motor Modes | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus-RTU Register | Modbus-RTU Register - Legacy | Modbus-TCP Register | Ethernet IP Register | Ethercat Register | BACnet MS/TP Register | Profinet Register |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P-35.0 | DA4 Minimum V / mA | 0.0 | 20.0 | 0.0 | V/mA | RW | - | - | - | - | 2087 | 0 | 135 | - | - | - | - | - | - |
P-35.1 | DA4 Maximum V / mA | 0.0 | 20.0 | 10.0 | V/mA | RW | - | - | - | - | 2087 | - | 11351 | - | - | - | - | - | - |
P-35.2 | DA4 Minimum Speed | -P-01 | P-01 | 0.00 | Hz/RPM | RW | - | - | - | - | 2087 | 2 | 11352 | - | - | - | - | - | - |
P-35.3 | DA4 Maximum Speed | -P-01 | P-01 | 50.00 | Hz/RPM | RW | - | - | - | - | 2087 | 3 | 11353 | - | - | - | - | - | - |
The above parameters are active when Analog Input 1 (DA4) Format (P‑16.0) is set to scaled voltage or scaled current and are used to scale and offset the connected signal. Example : 2-8VDC signal, where 2V is 0Hz and 8V is 40Hz. Set : P-16.0 = U Scal, P-35.0 = 2.0V, P-35.1 = 8.0V, P-35.2 = 0.00Hz, P-35.3 = 40.00Hz. | |||||||||||||||||||
P-35.4 | Master Follower Speed Scaling | 0.0 | 2000.0 | 100.0 | % | RW | - | - | - | - | 2087 | 4 | 11354 | - | - | - | - | - | - |
When operating in Master Follower Mode (P-12.0 = 7), the operating speed of the drive will be the Master speed multiplied by this factor, limited by the minimum and maximum speeds. | |||||||||||||||||||
Tip
For more information on DA4 setup > Using a Voltage signal to control Motor Speed
For more information on Master Follower > Master Follower Operation