Par.

Description

Minimum

Maximum

Default

Units

Access

Change During Run

Available Motor Modes

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus-RTU Register

Modbus-RTU Register - Legacy

Modbus-TCP Register

Ethernet IP Register

Ethercat Register

BACnet MS/TP Register

Profinet Register

P-35.0

DA4 Minimum V / mA

0.0

20.0

0.0

V/mA

RW

-

-

-

-

2087

0

135

-

-

-

-

-

-

P-35.1

DA4 Maximum V / mA

0.0

20.0

10.0

V/mA

RW

-

-

-

-

2087

-

11351

-

-

-

-

-

-

P-35.2

DA4 Minimum Speed

-P-01

P-01

0.00

Hz/RPM

RW

-

-

-

-

2087

2

11352

-

-

-

-

-

-

P-35.3

DA4 Maximum Speed

-P-01

P-01

50.00

Hz/RPM

RW

-

-

-

-

2087

3

11353

-

-

-

-

-

-

The above parameters are active when Analog Input 1 (DA4) Format (P‑16.0) is set to scaled voltage or scaled current and are used to scale and offset the connected signal.

Example : 2-8VDC signal, where 2V is 0Hz and 8V is 40Hz.

Set : P-16.0 = U Scal, P-35.0 = 2.0V, P-35.1 = 8.0V, P-35.2 = 0.00Hz, P-35.3 = 40.00Hz.

P-35.4

Master Follower Speed Scaling

0.0

2000.0

100.0

%

RW

-

-

-

-

2087

4

11354

-

-

-

-

-

-

When operating in Master Follower Mode (P-12.0 = 7), the operating speed of the drive will be the Master speed multiplied by this factor, limited by the minimum and maximum speeds.