P-15..P-19 I/O Setup

I/O Setup

Par.

Description

Minimum

Maximum

Default

Units

Access

Change During Run

Available Motor Modes

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus-RTU Register

Modbus-RTU Register - Legacy

Modbus-TCP Register

Ethernet IP Register

Ethercat Register

BACnet MS/TP Register

Profinet Register

P-15

Digital Inputs Function Select

-1

-

0

-

RW

-

-

-

-

2073

0

115

-

-

-

-

-

-

Provides a terminal macro system to pre‑define how each control terminal operates. Select the one most appropriate to the control and feedback signals that your system has.

Terminal functions are defined in accordance with the table shown in Terminal Macros, page.Terminal Macros

P-16.0

DA4 Analog Input 1 Format

0

6

U 0-10

-

RW

-

-

-

-

2074

0

116

-

-

-

-

-

-

0 (U 0-10): 0-10V

1 (U ScAL): Scaled Voltage Mode (Based on P-35 values)

2 (A 0-20): 0-20mA

3 (A 4-20): 4-20mA

4 (A ScAL): Scaled Current Mode (Based on P-35 values)

5 (PtC-th): PTC Thermistor input

6 (tY-th): KTY Thermistor Input

P-16.1

DA4 Analog Input 1 Invert

0

1

0

-

RW

-

-

-

-

2074

1

11161

-

-

-

-

-

-

If set to 1 then Analog Input 1 (DA4) signal is internally inverted, i.e.0‑10 V (0V=0Hz & 10V=50Hz) becomes 10‑0 V (0V=50Hz & 10V=0Hz).

0: Direct (0-10V, 4-20mA)

1: Inverse (10-0V, 20-0mA)

P-16.2

DA4 Analog Input 1 Signal Loss Reaction

0

3

trIP

-

RW

-

-

-

-

2074

2

11162

-

-

-

-

-

-

Defines the action when a 4‑20 mA signal connected to Analog Input 1 (DA4) is & <3 mA.

0 (trIP): Trip

1 (rP): Ramp To Stop (P-04.x)

2 (Pr1): Run at preset speed 1 (P-20)

3 (nonE): No Action (e.g. if Analog Input 1 (DA4) used for FB external I/O)

P-17.0

Maximum Switching Frequency

Rating Dependent

Rating Dependent

Rating Dependent

Rating Dependent

RW

-

-

-

-

2075

0

117

-

-

-

-

-

-

P-17.1

Minimum Switching Frequency

Rating Dependent

Rating Dependent

Rating Dependent

Rating Dependent

RW

-

-

-

-

2075

1

11171

-

-

-

-

-

-

P-17.2

PWM Modulation Type

0

2

0

-

RW

-

-

-

-

2075

2

11172

-

-

-

-

-

-

0: 3 Phase Modulation

1: 2 Phase Modulation

2: Auto Mode (Based on P-17.3)

P-17.3

PWM Modulation Changeover Speed

0.00

P-01

0.00

-

RW

-

-

-

-

2075

3

11173

-

-

-

-

-

-

P-18

Relay 1 Function Select

0

17

1

-

RW

-

-

-

-

2076

0

118

-

-

-

-

-

-

Logic 1 (C to NO Closes) when :

0: Drive Enabled

1: Drive Healthy

2: At Target Speed

3: Drive Tripped

4: Motor Speed >= Limit

5: Motor Current >= Limit

6: Motor Speed < Limit

7: Motor Current < Limit

8: Analog Input 2 (DA3) > Limit

9: Drive Ready to run

10: Fire Mode Active

11: Motor Speed > Limit AND NOT Fire Mode

12: Fieldbus Control - user bit 1

13: Fieldbus Control - user bit 2

14: Motor Torque >/= limit

15: STO Status

16: Service Indicator

17: Alarm Active

NOTE: "Limit" is defined by the values set in P-19.0 and P-19.1 and must be used together to control the behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in P-19.0 and return to Logic 0 when the signal falls below the value in P-19.1

P-19.0

Relay 1 Upper Threshold

0.0

200.0

100.0

%

RW

-

-

-

-

2077

0

119

-

-

-

-

-

-

P-19.1

Relay 1 Lower Threshold

0.0

100.0

0.0

%

RW

-

-

-

-

2077

1

11191

-

-

-

-

-

-

P-19.2

Digital/Relay Output Hysteresis

0.0

25.0

0.3

%

RW

-

-

-

-

2077

2

11192

-

-

-

-

-

-

Defines how close the motor speed must be to the target speed before the "At Target Speed" output is activated when assigned to P-18 or P-25.1.

P-19.3

AD1 Upper Threshold

0.0

200.0

100.0

%

RW

-

-

-

-

2077

3

11193

-

-

-

-

-

-

P-19.4

AD1 Lower Threshold

0.0

100.0

0.0

%

RW

-

-

-

-

2077

4

11194

-

-

-

-

-

-

NOTE: P-19.3 and P-19.4 are only valid when AD1 output is set for digital output mode (P-25.0 = dig).