CANopen Setup & Connecting to the Drive
CANopen - Physical Connection & Wiring
The drive has a built-in RJ45 port for connection of a CANopen network, this is highlighted by the circle in the image below.
![]() CautionAlways ensure 0V connection is present. NoticeA Network terminating resistor (120Ω) may be used at the end of the network to reduce noise. |
Check | Notes | |||||||||
|---|---|---|---|---|---|---|---|---|---|---|
Checking the Drives RJ45 port/ connection cable | Measure the CAN+ & CAN- pins voltage between 0V to check if they are working.
|
CANopen - Parameter Access Reading/Writing Parameters
All parameters can be accessed over CAN communication regardless of setting in P-12.
Access Parameters Information
To read or write to drive parameters you need to know the Object ID of that parameter. There are 3 different ways to find the Object ID of a parameter:
Documentation
Electronic Data Sheet (EDS) downloadable file from website: CANopen EDS File
Using the formula: Object ID = 2064h + Parameter Number.
Note
For Sub indexes use the formula and then the required sub index so for P-12.1 would be 2070 sub 1.
CANopen - Communication & Drive Control Setup Parameters
The following Parameters must be set in the drive for CANopen communication to read & write to Parameters:
Set the Primary Command Source in P-12.0.
Par.
Description
Minimum
Maximum
Default
Units
P-12.0
Control Source
0
8
tEr
-
Selects the command source of the drive i.e where the start/stop command comes from.
0 (tEr): Terminal only
1 (PAd-1): Keypad Only - Uni-Directional
2 (Pad-2): Keypad Only - Bi-Directional
3 (nEt): Communications network using Internal ramps (P-04.x)
4 (nEt-r): Communications network using network ramps
5 (Pi): PI Mode
6 (PiAS): PI Analog Summation
7 (FoL): Master Follower Mode
8 (OtP): Optitools-Pro Control
Set the Fieldbus Source in P-12.3.
Par.
Description
Minimum
Maximum
Default
Units
P-12.3
Communications Source
0
3
rtU
-
Selects which communications network source to use when P-12.0 is set to 3 or 4.
0 (rtU): Modbus RTU
1 (CAn): CANopen
2 (FbUS): Fieldbus Option Module if inserted
Set the CANopen Address in P-68.0. When set to the default (0) CANbus is disabled.
Par.
Description
Minimum
Maximum
Default
Units
P-68.0
CANopen Address
0
127
0
-
Set the CANopen Baud Rate in P-68.1.
This value must match the other devices on the systems values.
Par.
Description
Minimum
Maximum
Default
Units
P-68.1
CANopen Baud Rate
0
3
2
kbps
0 (125) : 125kbps
1 (250) : 250kbps
2 (500) : 500kbps
3 (1000) : 1Mbps