DC Bus Discharge times
DC Bus discharge times are based on maximum rated DC bus voltage.
Note
In compliance with EN 61800-5-1:2007 all drives have a caution on the rating labels stating that, following a mains power down 10mins should be allowed before removing any drive cover.
WARNING – Risk of electric shock
Hazardous voltage remains on the DC bus after the mains supply is disconnected. Wait at least 10 minutes after power-down before removing any drive cover. This complies with EN 61800-5-1, and a corresponding caution appears on the drive rating label.
DC Bus Discharge Times
Frame Size | Voltage Rating (VAC) | Power Rating (kW) | Max (Vdc) | After 5s (Vdc) | After 60s (Vdc) | Time to reach 50Vdc (s) |
|---|---|---|---|---|---|---|
1 | 180-240VAC | 0.37 | 373 | 298 | 9 | 16 |
1 | 180-240VAC | 0.75 & 1.5 | 373 | 340 | 22 | 32 |