DC Bus Discharge times

DC Bus discharge times are based on maximum rated DC bus voltage.

Note

In compliance with EN 61800-5-1:2007 all drives have a caution on the rating labels stating that, following a mains power down 10mins should be allowed before removing any drive cover.

WARNING – Risk of electric shock

Hazardous voltage remains on the DC bus after the mains supply is disconnected. Wait at least 10 minutes after power-down before removing any drive cover. This complies with EN 61800-5-1, and a corresponding caution appears on the drive rating label.

DC Bus Discharge Times

Frame Size

Voltage Rating (VAC)

Power Rating (kW)

Max (Vdc)

After 5s (Vdc)

After 60s (Vdc)

Time to reach 50Vdc (s)

1

180-240VAC

0.37

373

298

9

16

1

180-240VAC

0.75 & 1.5

373

340

22

32