P-47 DA3 Analog Input 2 Setup

DA3 Analog Input 2 Setup

Par.

Description

Minimum

Maximum

Default

Units

Access

Change During Run

Available Motor Modes

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus-RTU Register

Modbus-RTU Register - Legacy

Modbus-TCP Register

Ethernet IP Register

Ethercat Register

BACnet MS/TP Register

Profinet Register

P-47.0

Analog Input 2 (DA3) Format

0

6

U 0-10

-

RW

-

-

-

-

2093

0

147

-

-

-

-

-

-

0 (U 0-10): 0-10V

1 (U ScAL): Scaled Voltage Mode (Based on P-58 values)

2 (A 0-20): 0-20mA

3 (A 4-20): 4-20mA

4 (A ScAL): Scaled Current Mode (Based on P-58 values)

5 (PtC-th): PTC Thermistor input

6 (tY-th): KTY Thermistor Input

P-47.1

Analog Input 2 (DA3) Invert

0

1

0

-

RW

-

-

-

-

2093

1

11471

-

-

-

-

-

-

0: Direct (0-10V, 4-20mA)

1: Inverse (10-0V, 20-0mA)

P-47.2

Analog Input 2 (DA3) Signal Loss (4-20mA only) when <3mA

0

3

trIP

-

RW

-

-

-

-

2093

2

11472

-

-

-

-

-

-

0 (trIP): Trip

1 (rP): Ramp To Stop (P-04.x)

2 (Pr1): Run at preset speed 1 (P-20)

3 (nonE): No Action (e.g. if Analog Input 1 (DA4) used for FB external I/O)