Skip to main content

E4 Help Desk

PI Operation

Before Starting

  • Connect the necessary feedback signals to the drive. e.g. pressure transducer.

    Transducer_connections.svg

    Note

    Example above shows connection of a 2-wire or loop Powered Transducer (Left) and a 3 or 4 Wire Transducer (Right)

  • Ensure the motor is commissioned.

Programming

  1. Enable PI Control Mode by Setting parameter P-12.0 to 5

  2. Enter the Feedback Transducer type in parameter P-47.0 e.g. 0-10V

  3. Enter the Feedback Transducer Minimum signal in parameter P-46.2 e.g 2.0 bar when at 0V

  4. Enter the Feedback Transducer Maximum signal in parameter P-46.3 e.g 10.0 bar when at 0V

  5. Define the PI reference Setpoint source in parameter P-44

  6. Once a start signal is provided the drive will run in PI mode.

  7. Define if the system is Direct Operation or Inverse Operation in parameter P-46.1 (see note below)

Note

P-46.1 = 0 Direct Operation, the motor speed will increase when the measured value from the feedback drops

P-46.1 = 1 Inverse Operation, the motor speed will decrease when the measured value from the feedback drops.

Once the values in parameters P46.2 and P46.3 have been entered all set point and feedback values are in real units to match the connected sensor e.g. Bar

PID_Diagram.svg

Note

Example above shows a setup for maintaining pressure in a pumping system, where the Setpoint is a fixed value and the feedback is a 0-10V pressure transducer connected to terminal DA3 (Analog input 2) .

Tuning

  • Parameter P-41 and P-42 can be used to fine tune the system performance.

  • Tuning P-41 (Proportional Gain)

    • Function: This parameter determines how much the drive's output frequency changes in response to small changes in the feedback signal.

    • Stability Impact: Higher values make the drive more sensitive and responsive to errors. However, setting this value too high can cause system instability and oscillation.

    • Tuning Strategy: Start with the default value of 1.0. If the system is too slow to reach the set point, increase the value incrementally. If the motor begins to hunt or oscillate rapidly around the target, decrease the value to restore stability.

  • Tuning P-42 (Integral Time)

    • Function: This parameter determines how the controller accounts for errors over time to reach the exact set point.

    • Stability Impact: Larger values provide a more damped response, which is essential for systems where the overall process (such as a large tank filling or a slow-moving temperature change) responds slowly

    • Tuning Strategy: Start with the default value of 1.0s. If the system overshoots the target or is unstable, increase the integral time to slow down the corrective action and stabilize the process

Standby Mode

  1. Set the Standby Time

    Set P-48.0 to the time the drive must run below the speed set in P-48.1 before entering standby and stopping the motor.

    Example: P-48.0 = 20.0 s.

  2. Set the Wake-Up Level

    Set P-49 to the percentage change in PI feedback required to wake the drive. (percentage change is the % difference between setpoint and feedback.

    Example: P-49 = 5.0%.

    Note

    How it works

    When the drive is in standby, a drop in PI feedback increases the PI demand. When the PI error reaches the wake-up level set in P-49, the drive restarts the motor to return the feedback to the required setpoint.

    The response when waking also depends on P-43.2 :

    P-43.2 = 0 : PI output starts at 0% and builds as required, giving a more gradual response.

    P-43.2 = 1 : PI output starts at 100%, giving a faster, more aggressive response.

    Example: For a pressure-controlled pump, when the pressure falls, the pump speed increases to restore the required pressure. With P-43.2 = 1, the pump starts with a high PI demand when waking from standby. With P-43.2 = 0, the PI output builds according to the actual pressure error, giving a more gradual response.

Parameter

Sub-Index

Description

Minimum

Maximum

Default

Units

P-41

-

PI Controller Proportional Gain

0.0

30.0

1.0

-

P-42

-

PI Controller Integral Time

0.0

30.0

1.0

s

P-43

P-43.0

PI Operation

Setting

Function

0

Discontinuous. On disable, PI controller disabled.

1

Continuous. PI runs continually regardless of drive state

0

1

0

-

P-43.1

PI Mode

Setting

Function

0

Direct

1

Inverse

0

1

0

-

P-43.2

PI Wake Mode

Defines if the PI output starts at minimum or maximum on waking from standby.

Note

Function only works if value set in P-49 is greater than 0.0

Setting

Function

0

Wake at Minimum

1

Wake at Maximum

0

1

0

-

P-44

-

PI Reference (Setpoint) Source Select

Setting

Function

0

Digital Fixed values (P-45 Used)

1

Analog Input

2

Fieldbus Process Data

0

2

0

-

P-45

-

PI Fixed Reference

P-46.2

P-46.3

0.0

Real Units based on setting of P-46.2 and P-46.3

P-46

P-46.0

PI Feedback Source

Setting

Function

0

Analog Input 2 (Terminal DA3)

1

Analog Input 1 (Terminal DA4)

2

Motor Load Current

3

DC Bus Voltage

4

1st Analog Input 1 (DA4) - 2nd Analog Input 2 (DA3)

5

Maximum Value between Analog Input 1 (DA4) and Analog Input 2 (DA3)

0

5

0

-

P-46.1

PI Feedback Function

Setting

Function

0

Direct Operation

1

Inverse Operation

0

1

0

-

P-46.2

PI Feedback Sensor Minimum Signal

-65535

65535

0

-

P-46.3

PI Feedback Sensor Maximum Signal

-65535

65535

0

-

P-48

P-48.0

Standby Delay

0.0

250.0

0.0

S

P-48.1

Standby activation speed

0.0

50.0

0.0

Hz/RPM

P-49

-

PI Wake Up Error Level

0.0

100.0

5.0

%

Parameter

Sub-Index

Description

P0-17

Read Only

P0-17.0

PI Reference

Displays the PI reference value in real units

P0-17.1

PI Feedback

Displays the PI feedback value in real units

P0-17.2

PI Output

Problem

Solution

How do I know when the drive is in standby mode?

When the drive enters standby state, the drive output to the motor is disabled, and the display shows the message "stndby".

Drive is not going into Standby?

Check P-48 is >0