P-20..P-25 Preset Speeds, Fast Stop & Control Outputs
Preset Speeds, Fast Stop & Control Outputs
Par. | Description | Minimum | Maximum | Default | Units | Access | Change During Run | Available Motor Modes | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus-RTU Register | Modbus-RTU Register - Legacy | Modbus-TCP Register | Ethernet IP Register | Ethercat Register | BACnet MS/TP Register | Profinet Register | |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
P-20 | Preset / Jog Frequency / Speed 1 | P-02 | P-01 | 5.0 | Hz/RPM | RW | - | - | - | - | 2078 | 0 | 120 | - | - | - | - | - | - | |
P-21 | Preset / Jog Frequency / Speed 2 | P-02 | P-01 | 25.00 | Hz/RPM | RW | - | - | - | - | 2079 | 0 | 121 | - | - | - | - | - | - | |
P-22 | Preset / Jog Frequency / Speed 3 | P-02 | P-01 | 40.00 | Hz/RPM | RW | - | - | - | - | 207A | 0 | 122 | - | - | - | - | - | - | |
P-23 | Preset / Jog Frequency / Speed 4 | P-02 | P-01 | 50.00 | Hz/RPM | RW | - | - | - | - | 207B | 0 | 123 | - | - | - | - | - | - | |
P-24 | 2nd Ramp Time (Fast Stop) | 0.00 | 600.00 | 1.00 | s | RW | - | - | - | - | 207C | 0 | 124 | - | - | - | - | - | - | |
This ramp time is automatically selected in the case of a mains power loss if P-05.1 = 2. When using a setting of P-15 that provides a “Fast Stop” function, this ramp time is also used. When set to 0.00, the drive will coast to stop. | ||||||||||||||||||||
P-25.0 | AD1 Output Type | 0 | 1 | dig | - | RW | - | - | - | - | 207D | 0 | 125 | - | - | - | - | - | - | |
| ||||||||||||||||||||
P-25.1 | AD1 Digital Output Function Select | 0 | 17 | 2 | - | RW | - | - | - | - | 207D | 1 | 11251 | - | - | - | - | - | - | |
| ||||||||||||||||||||
NOTE: "Limit" is defined by the values set in P-19.3 and P-19.4 and must be used together to control the behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in P-19.3 and return to Logic 0 when the signal falls below the value in P-19.4. | ||||||||||||||||||||
P-25.2 | AD1 Digital Output Invert | 0 | 1 | 0 | - | RW | - | - | - | - | 207D | 2 | 11252 | - | - | - | - | - | - | |
| ||||||||||||||||||||
P-25.3 | AD1 Analog Output Function Select | 0 | 5 | 0 | - | RW | - | - | - | - | 207D | 3 | 11253 | - | - | - | - | - | - | |
| ||||||||||||||||||||
P-25.4 | AD1 Analog Output Format | 0 | 5 | U 0-10 | - | RW | - | - | - | - | 207D | 4 | 11254 | - | - | - | - | - | - | |
| ||||||||||||||||||||