Terminal Control
How Terminal Mode Works
When P-12 = 0, the drive operates in Terminal Mode and is controlled through signals connected to the control terminals. The selected Terminal Macro (P-15) defines how the digital and analog inputs are assigned for the required control method, including functions such as start/stop, directional control, and speed reference selection or adjustment.
Default Macro is shown below
|
Terminal Macro Terms and Definitions
Term | Meaning |
|---|---|
Digital Input (DI) | A Digital control input |
Digital/Analog (DA) | A Digital/Analog control input |
Analog Input (AI) | Analog reference that provides a variable reference |
Preset Speed Reference (PR) | A fixed Preset Speed Reference stored within the drive. These can be found in P-20 - P-23. |
Keypad Reference (KPD Ref) | Speed reference via the keypad on the drive. |
External Trip (E-Trip) | Input can be used to trip drive when an external fault condition occurs. |
Selecting a Terminal Macro
Choose the macro that best matches the application.
Select View to see each macro’s functionality, terminal connections and an example application.
P-15 | Analog Speed Reference | Preset Speeds | Forward / Reverse Direction Change | External Trip Input | Fast Stop | Fire Mode | Wiring & Examples |
|---|---|---|---|---|---|---|---|
0 | ✓ | 1 | ✓ | ||||
1 | ✓ | 2 | |||||
2 | 4 | ||||||
3 | ✓ | 1 | ✓ | ||||
4 | ✓ (2) | ||||||
5 | ✓ | 1 | ✓ | ||||
6 | ✓ | ✓ | |||||
7 | ✓ | ✓ | ✓ | ||||
8 | 4 | ✓ | |||||
9 | 4 | ✓ | |||||
10 | ✓ | 1 | |||||
11 | ✓ | ✓ | |||||
12 | ✓ | 1 | ✓ | ||||
13 | ✓ | 1 | ✓ | ||||
14 | ✓ | 2 | ✓ | ||||
15 | ✓ | 1 | ✓ | ||||
16 | ✓ | 1 | ✓ | ✓ | |||
17 | 4 | ✓ | |||||
18 | ✓ | ✓ | ✓ | ||||
19 | ✓ | 1 | ✓ |
Related Parameters
Parameter | Function |
|---|---|
P-12.x | Selects the primary control method and determines how the drive speed reference is generated. |
P-15 - (0-19) | Selects the terminal macro and automatically assigns functions to the digital and analog inputs. |
P-16.0 | Selects the format of Analog Input 1 (e.g. 0–10 V, 4–20 mA). |
P-20 to P-23 | Preset speed parameters |
P-30 .3 to .5 | Fire mode parameters |
P-47.0 | Selects the format of Analog Input 2 (e.g. 0–10 V, 4–20 mA). |
Terminal → | DI1 | DI2 | DA3 | DA4 | ||||||
P-15 ↓ | 0 | 1 | 0 | 1 | 0 | 1 | 0 | 1 | ||
0 | STOP | RUN | FWD ↻ | REV ↺ | Ref 1 (DA4) | Ref 2 (P-20) | Analog Input (DA4) | |||
1 | STOP | RUN | Ref 1 (DA4) | Ref 2 (PR - DA3) | P-20 | P-21 | Analog Input (DA4) | |||
2 | STOP | RUN | DI2 | DA3 | PR | P-20 - P-23 | P-01 | |||
0 | 0 | P-20 | ||||||||
1 | 0 | P-21 | ||||||||
0 | 1 | P-22 | ||||||||
1 | 1 | P-23 | ||||||||
3 | STOP | RUN | Ref 1 (DA4) | Ref 2 (P-20) | E-TRIP | OK | Analog Input (DA4) | |||
4 | STOP | RUN | Ref 1 (DA4) | Ref 2 (DA3) | Analog Input (DA3) | Analog Input (DA4) | ||||
5 | STOP | RUN FWD ↻ | STOP | RUN REV ↺ | Ref 1 (DA4) | Ref 2 (P-20) | Analog Input (DA4) | |||
˄--------FAST STOP (P-24)--------˄ | ||||||||||
6 | STOP | RUN | FWD ↻ | REV ↺ | E-TRIP | OK | Analog Input (DA4) | |||
7 | STOP | RUN FWD ↻ | STOP | RUN REV ↺ | E-TRIP | OK | Analog Input (DA4) | |||
˄--------FAST STOP (P-24)--------˄ | ||||||||||
8 | STOP | RUN | FWD ↻ | REV ↺ | DA3 | DA4 | Preset Speed | |||
0 | 0 | P-20 | ||||||||
1 | 0 | P-21 | ||||||||
0 | 1 | P-22 | ||||||||
1 | 1 | P-23 | ||||||||
9 | STOP | START FWD ↻ | STOP | START REV ↺ | DA3 | DA4 | Preset Speed | |||
˄----------FAST STOP (P-24)----------˄ | 0 | 0 | P-20 | |||||||
1 | 0 | P-21 | ||||||||
0 | 1 | P-22 | ||||||||
1 | 1 | P-23 | ||||||||
10 | (NO) | START ⬏ | STOP | (NC) | Ref 1 (DA4) | Ref 2 (P-20) | Analog Input (DA4) | |||
11 | (NO) | START ⬏ FWD ↻ | STOP | (NC) | (NO) | START ⬏ REV ↺ | Analog Input (DA4) | |||
˄-------------------FAST STOP (P-24)-------------------˄ | ||||||||||
12 | STOP | RUN | FAST STOP (P-24) | OK | Ref 1 (DA4) | Ref 2 (P-20) | Analog Input (DA4) | |||
13 | (NO) | START FWD ↻ | STOP | (NC) | (NO) | START REV ↺ | Ref 1 (KPD) | Ref 2 (P-20) | ||
˄---------------------FAST STOP (P-24)---------------------˄ | ||||||||||
14 | STOP | RUN | DI2 | E-TRIP | OK | DI2 | DA4 | Preset Speed | ||
0 | 0 | P-20 | ||||||||
1 | 0 | P-21 | ||||||||
0 | 1 | P-22 | ||||||||
1 | 1 | P-23 | ||||||||
15 | STOP | RUN | Ref 1 (P-23) | Ref 2 (DA4) | Fire Mode | Analog Input (DA4) | ||||
16 | STOP | RUN | Ref 1 (P-23) | Ref 2 (P-21) | Fire Mode | FWD ↻ | REV ↺ | |||
17 | STOP | RUN | DI2 | Fire Mode | DI2 | DA4 | Preset Speed | |||
0 | 0 | P-20 | ||||||||
1 | 0 | P-21 | ||||||||
0 | 1 | P-22 | ||||||||
1 | 1 | P-23 | ||||||||
18 | STOP | RUN | FWD ↻ | REV ↺ | Fire Mode | Analog Input (DA4) | ||||
19 | STOP | RUN | Ref 1 (DA4) | Ref 2 (P-20) | Not Fire Mode | Fire Mode | Analog Input (DA4) | |||
NOTE | When P-15 = 19, P-30.3 and P-30.4 have no effect. When the fire mode input is on, the drive will run regardless of whether the run input is present. Speed reference in Fire Mode is the value set in Fire Mode speed parameter P-30.5. If P-30.5 is 0 (default) then the drive will run either at DA4 (AI1) or Preset speed 1 (P-20) depending upon DI2 state. | |||||||||
Note
All examples are based off the default parameter settings. Functionality of Macros, such as Fire Mode Latching, can be changed using appropriate settings.
Macro (P-15) | Functionality | Terminal Connections | Example Application |
|---|---|---|---|
0 | Stop/Run control from DI1. Forward and reverse direction control using DI2. Selection between the DA4 analog reference and preset speed P-20 using DA3. DA4 is used as the analog speed reference. | ![]() | A reversible conveyor is started and stopped using DI1. DI2 selects the direction, while DA3 switches between the DA4 analog speed reference and preset speed P-20. |
1 | Stop/Run control from DI1. Selection between the DA4 analog reference and preset speed control using DI2. Selection between preset speeds P-20 and P-21 using DA3. DA4 is used as the analog speed reference. | ![]() | A conveyor normally uses an analog speed reference from DA4. DI2 selects preset speed control when a fixed production speed is required, and DA3 selects between preset speeds P-20 and P-21. |
2 | Stop/Run control from DI1. Selection between preset speeds P-20 to P-23 using DI2 and DA3. DA4 selects between the chosen preset speed and maximum speed P-01. | ![]() | A process requires four selectable operating speeds. DI2 and DA3 select preset speeds P-20 to P-23, while DA4 selects maximum speed P-01 when full-speed operation is required. |
3 | Stop/Run control from DI1. Selection between the DA4 analog reference and preset speed P-20 using DI2. External trip input using DA3. DA4 is used as the analog speed reference. | ![]() | A conveyor normally uses an analog speed reference from DA4. DI2 selects preset speed P-20 for fixed-speed operation, while a protective device connected to DA3 can stop the drive if an external fault occurs. |
4 | Stop/Run control from DI1. Selection between the DA3 and DA4 analog references using DI2. AI2 is connected through DA3 and AI1 is connected through DA4. | ![]() | A pump can be controlled from either of two external analog signals. DI2 selects between the DA3 and DA4 speed references, allowing control to be transferred between two controllers or process signals. |
5 | Run forward control from DI1 and run reverse control from DI2. Fast Stop using the P-24 deceleration time is enabled when DI1 and DI2 are both active. Selection between the DA4 analog reference and preset speed P-20 using DA3. DA4 is used as the analog speed reference. | ![]() | A reversible conveyor uses separate forward and reverse commands. If both commands are applied, the drive performs a Fast Stop using the P-24 deceleration time. DA3 selects between analog speed control and preset speed P-20. |
6 | Stop/Run control from DI1. Forward and reverse direction control using DI2. External trip input using DA3. DA4 is used as the analog speed reference. | ![]() | A reversible conveyor is started and stopped using DI1 and changes direction using DI2. A protective device connected to DA3 can stop the drive if an external fault occurs, while DA4 controls the operating speed. |
7 | Run forward control from DI1 and run reverse control from DI2. Fast Stop using the P-24 deceleration time is enabled when DI1 and DI2 are both active. External trip input using DA3. DA4 is used as the analog speed reference. | ![]() | A reversible machine uses separate forward and reverse commands. Applying both commands performs a Fast Stop, while a protective device connected to DA3 can stop the drive if an external fault occurs. |
8 | Stop/Run control from DI1. Forward and reverse direction control using DI2. Selection between preset speeds P-20 to P-23 using DA3 and DA4. | ![]() | A reversible conveyor requires four fixed operating speeds. DI2 selects direction, while DA3 and DA4 select preset speeds P-20 to P-23. |
9 | Run forward control from DI1 and run reverse control from DI2. Fast Stop using the P-24 deceleration time is enabled when DI1 and DI2 are both active. Selection between preset speeds P-20 to P-23 using DA3 and DA4. | ![]() | A reversible machine uses separate forward and reverse commands and four selectable preset speeds. Applying both direction commands performs a Fast Stop using the P-24 deceleration time. |
10 | Three-wire Start/Stop control using normally open and normally closed contacts connected to DI1 and DI2. Selection between the DA4 analog reference and preset speed P-20 using DA3. DA4 is used as the analog speed reference. | ![]() | A machine uses separate momentary Start and Stop push buttons. DA3 selects between external analog speed control from DA4 and preset speed P-20. |
11 | Three-wire forward and reverse control using DI1, DI2 and DA3. Fast Stop using the P-24 deceleration time is enabled when forward and reverse start commands are both active. DA4 is used as the analog speed reference. | ![]() | A reversible machine uses momentary forward and reverse Start push buttons with a common Stop input. If both direction commands are applied, the drive performs a Fast Stop. |
12 | Stop/Run control from DI1. Fast Stop using the P-24 deceleration time from DI2. Selection between the DA4 analog reference and preset speed P-20 using DA3. DA4 is used as the analog speed reference. | ![]() | A conveyor is started and stopped using DI1. DI2 provides a dedicated Fast Stop input, while DA3 selects between the DA4 analog reference and preset speed P-20. |
13 | Three-wire forward and reverse control using DI1, DI2 and DA3. Fast Stop using the P-24 deceleration time is enabled when forward and reverse start commands are both active. Selection between the keypad reference and preset speed P-20 using DA4. | ![]() | A reversible machine uses momentary forward and reverse Start push buttons with a common Stop input. DA4 selects between keypad speed control and preset speed P-20. |
14 | Stop/Run control from DI1. Selection between preset speeds P-20 to P-23 using DI2 and DA4. External trip input using DA3. | ![]() | A machine requires four preset operating speeds. DI2 and DA4 select preset speeds P-20 to P-23, while a protective device connected to DA3 can stop the drive if an external fault occurs. |
15 | Stop/Run control from DI1. Selection between preset speed P-23 and the DA4 analog reference using DI2. Fire Mode control using DA3. DA4 is used as the analog speed reference. | ![]() | A smoke-extract fan normally uses preset speed P-23 or an external analog reference from DA4. DI2 selects the speed reference, while DA3 activates Fire Mode when required. |
16 | Stop/Run control from DI1. Selection between preset speeds P-23 and P-21 using DI2. Fire Mode control using DA3. Forward and reverse direction control using DA4. | ![]() | A reversible smoke-control fan operates at one of two preset speeds. DI2 selects between P-23 and P-21, DA4 selects direction, and DA3 activates Fire Mode. |
17 | Stop/Run control from DI1. Selection between preset speeds P-20 to P-23 using DI2 and DA4. Fire Mode control using DA3. | ![]() | A smoke-control fan requires four selectable preset speeds during normal operation. DI2 and DA4 select speeds P-20 to P-23, while DA3 activates Fire Mode. |
18 | Stop/Run control from DI1. Forward and reverse direction control using DI2. Fire Mode control using DA3. DA4 is used as the analog speed reference. | ![]() | A tunnel ventilation fan uses DA4 for speed control and DI2 for reversible airflow. When a fire signal is applied through DA3, Fire Mode maintains operation for smoke control. |
19 | Stop/Run control from DI1. Selection between the DA4 analog reference and preset speed P-20 using DI2. Fire Mode control using DA3. | ![]() | A smoke-extraction fan normally uses either the DA4 analog reference or preset speed P-20. When Fire Mode is activated through DA3, the drive runs using the Fire Mode behaviour and speed settings. |
Troubleshooting & FAQ's
Problem | Solution |
|---|---|