P-67 Optibus Port Parameters

Par.

Description

Minimum

Maximum

Default

Units

Access

Change During Run

Available Motor Modes

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus-RTU Register

Modbus-RTU Register - Legacy

Modbus-TCP Register

Ethernet IP Register

Ethercat Register

BACnet MS/TP Register

Profinet Register

P-67.0

Optibus Address

1

63

1

-

RW

-

-

-

-

20A7

0

167

-

-

-

-

-

-

P-67.1

Optibus Port Mode

0

2

P21

-

RW

-

-

-

-

20A7

1

11671

-

-

-

-

-

-

Value

Function

0 (nonE)

Port Disabled

1 (ObuS)

E3 Legacy compatibility mode

2 (P21)

E4 mode

P-67.2

Optibus Comms Loss Reaction

0

3

triP

-

RW

-

-

-

-

20A7

2

11672

-

-

-

-

-

-

Value

Reaction

0 (triP)

Trip (Coast Stop)

1 (rP)

Ramp to Stop (P-04.x)

2 (Pr1)

Run at Preset Speed 1 (P-20)

2 (nonE)

No action