DC Bus Voltage Protection Levels

The drive continuously monitors the DC bus voltage and includes built-in protection against over-voltage and under-voltage conditions. If the DC bus voltage exceeds or falls below the defined limits, the drive will trip to protect itself.

DC Bus Voltage Thresholds - 3 Phase Output Drives

Function

110-120VAC Input Drive

180-240VAC Input Drive

380-480VAC Input Drive

Braking Resistor Turn-On Voltage

Note

Size 1 does not support connection of a Braking resistor

390Vdc

390Vdc

780Vdc

Overvoltage Trip Level (O-Volt)

418Vdc

418Vdc

835Vdc

Undervoltage Trip Level (U-Volt)

160Vdc

160Vdc

320Vdc