The drive supports multiple operating modes, allowing the drive to be started and stopped using the keypad, control terminals, communications networks, application functions and external control systems.

The source of the run command is determined by the configured control source and associated settings.

Control Source Selection

The primary control method is selected using P-12.0 - Control Source.

This parameter determines where the drive receives its run and stop commands from.

Par.

Description

Minimum

Maximum

Default

Units

P-12.0

Control Source

0

8

tEr

-

Selects the command source of the drive i.e where does the start/stop command come from.

0 (tEr): Terminal only

1 (PAd-1): Keypad Only - Uni-Directional

2 (Pad-2): Keypad Only - Bi-Directional

3 (nEt): Communications network using Internal ramps

4 (nEt-r): Communications network using network ramps

5 (Pi): PI Mode

6 (PiAS): PI Analogue Summation

7 (FoL): Master Follower Mode

8 (OtP): Optitools-Pro Control

When P-12.0 is configured for keypad operation, P-12.4 - Keypad Mode Start Source determines how the drive is started and stopped while operating in keypad mode.

This allows the keypad operating behaviour to be adapted to application requirements and user preferences.

Par.

Description

Minimum

Maximum

Default

Units

P-12.4

Keypad Mode Command Source

0

2

0

-

Defines how the drive is started and stopped when in keypad mode (P-12.0 = 1).

0: Keypad Buttons Only

1: Keypad Buttons plus Digital Input needs to be active

2: Digital Input Only

When P-12.0 is configured for network operation, P-12.3 - Active Communications Network is used to select the communications interface that will control the drive.

Once selected, run/stop commands and speed references can be received from the active network.

Par.

Description

Minimum

Maximum

Default

Units

P-12.3

Communications Source

0

3

rtU

-

Selects which communications network source to use when P-12.0 is set to 3 or 4.

0 (rtU): Modbus RTU

1 (CAn): CANopen

2 (FbUS): Fieldbus Option Module if inserted