Skip to main content

E4 Help Desk

P-01..P-11 Basic Parameters

Basic Parameters

Par.

Description

Minimum

Maximum

Default

Units

P-01

Maximum Frequency / Speed Limit

P-02

500.0

50.0 (60.0)

Hz/RPM

P-02

Minimum Frequency / Speed Limit

0.00

P-01

0.00

Hz/RPM

P-03.0

Acceleration Ramp Time

0.00

600.0

5.00

s

Time taken for the motor speed to increase from 0 to Motor Rated Frequency (P-09).

P-03.1

Acceleration Ramp Time 2

0.00

600.0

2.00

s

P-03.2

Acceleration Ramp Switchover Speed

0.00

P-09

0.00

Hz/RPM

Speed at which the drive switches from Acceleration Ramp Time (P-03.0) to Acceleration Ramp Time 2 (P-03.1).

P-04.0

Deceleration Ramp Time

0.00

600.0

5.00

s

If set to 0.00 motor will coast to stop.

P-04.1

Deceleration Ramp Time on Stop Command

0.00

600.0

0.00

s

If set to 0.00 then P-04.0 is used.

P-05.0

Terminal & Keypad Stop Mode

0

3

0

-

Selects how the drive stops the motor following a stop command.

0 : Ramp to stop (P-04.x)

2 : Ramp to stop (P-04.x) with AC Flux braking

1 : Coast to stop

3 : Ramp to minimum speed (P-04.0) and then Coast

P-05.1

Mains Loss Reaction

0

3

rP

-

Determines the drive response when the mains supply is lost.

0 (rP) : Ramp to stop

1 (coASt) : Coast to Stop

2 (F-rP) : Fast Ramp (P-24) to stop

3 (triP) : No action drive trips mains loss (InLoSS)

P-05.2

DC Supply Enable

0

1

0

-

Enables operation from a DC power supply source connected to power terminals +DC/-DC.

0: Disabled

1: Enabled

P-06

Energy Optimiser

0

1

0

-

0: Disable

1: Enable

P-07

Motor Rated Voltage/Back EMF

0

250 / 500

230 / 400

V

Motor Rated Voltage (Induction Motor)/ Back EMF at rated speed (Synchronous Motors).

P-08

Motor Rated Current

Drive Rating Dependent

A

P-09

Motor Rated Frequency

5

500

50 (60)

Hz

P-10.0

Motor Rated Speed

0

30000

0

RPM

Entering motor nameplate value enables the slip compensation function. (V/F Mode only).

NOTE: If P-09 value is changed, P-10 value is reset to 0.

P-10.1

Operating Units

0

1

0

Hz/RPM

0: Hz

1: RPM (P-10.0 must also have been populated)

P-11.0

Boost Voltage

0.0

Rating Dependent

Drive Dependent

%

Applies additional voltage at low speeds to improve motor torque for Induction Motors operating in V/F mode.

If set to 0.0 the drive will automatically calculate the required Boost Voltage.

P-11.1

Torque Boost Current at Start (PM Motors)

0.0

Rating Dependent

10.0

%

P-11.2

Torque Boost Current at Start Frequency Limit (PM Motors)

0.0

Rating Dependent

10.0

%

P-11.3

Torque Boost Current at Stop (PM Motors)

0.0

Rating Dependent

10.0

%

P-11.4

Torque Boost Current Frequency Limit at Stop (PM Motors)

0.0

Rating Dependent

10.0

%

Tip

For more information on Ramps > Ramps

For more information on Motor Data > Commissioning an Induction Motor