Using a Current signal to control Motor Speed

Note

The below guidance assumes the motor data parameters have been entered and all other parameters are in a default state

Wiring the Analog Input

  1. Connect the Current signal source to the drive :

    Signal (+) → Terminal (DA4) & Signal (0V / GND) → Terminal 0V

Configure the signal type

  1. Select in parameter P16.0 the signal type

Signal Type

Value to set in P-16.0

Input Voltage vs Motor Speed

0-20mA

A 0-20

0mA = 0Hz / rpm

20mA = Maximum Speed (As per set in P-01)

4-20mA

A 4-20

4mA = 0Hz / rpm

20mA = Maximum Speed (As per set in P-01)

0-20mA (with Scaling)

A ScAL

See "Configure Scaling" below

Note

The drive will trip "4-20 F" if the current signal is 3mA or less (signal loss detection)

Configure Operating Mode (If required)

The operating mode determines if the motor speed should increase with an increasing Current signal or decrease.

Value set in P-16.1

Input Current vs Motor Speed

0

Motor Speed increases as Analog Input Current Increases e.g 0 to 20mA → 0 to 50Hz

1

Motor Speed Decreases as Analog Input Current Increases e.g 0 to 20mA → 50 to 0Hz

Configure Scaling of Current Signal (If required)

Typical linear example of analog input scaling is : 0mA → 0 Hz & 20mA → Maximum frequency (e.g. 50 Hz) but what if you want for example 2mA → 0 Hz & 10mA → 40 Hz ?

  1. P-16.0 (Analog Input 1 Format) : Set to "A ScaL" (defines terminal input type as scaled current mode)

  2. P-35.0 (DA3 Min V/mA) → Set to 2.0mA (This represents the 2mA as the motor speed start point of the current signal)

  3. P-35.1 (DA3 Max V/mA) → Set to 10.0mA (This represents the 10.0mA as the end point)

  4. P-35.2 (DA3 Min Speed) → Set to 0Hz (This sets the output to be 0Hz at 0mA)

  5. P-35.3 (DA3 Max Speed) →Set to 40Hz (This sets the output to be 40Hz at 10.0mA)

Signal loss detection

When the analog input is set to operate in current mode the drive can detect and react accordingly on signal loss (signal loss is defined as when the current is 3mA or less)

Value set in P-16.2

Drive Reaction

triP

Drive Trips 4-20 F and motor Coasts to Stop

rP

Pr1

nonE

Drive Ramps to 0

Troubleshooting & FAQ's

Problem

Solution