P-37..P-46 Access, Display Scaling & PI Control
Access, Display Scaling & PI Control
Par. | Description | Minimum | Maximum | Default | Units | |
|---|---|---|---|---|---|---|
P-37 | Level 2 Access Definition | 0 | 9999 | 0 | - | |
P-38 | Parameter Access Lock | 0 | 1 | 0 | - | |
| ||||||
P-39 | Positive/Negative Logic Select | 0 | 1 | 0 | - | |
| ||||||
| ||||||
P-40.0 | Display Scaling Source | 0 | 4 | 0 | - | |
| ||||||
P-40.1 | Display Scaling Factor | 0.000 | 30.000 | 0.000 | - | |
Allows the drive to display an alternative output unit scaled from an existing parameter, e.g., to display speed in metres per second based on the output frequency. Value taken from the data source set in Display Scaling Source (P‑40.0) is first multiplied by this value then divided by Display Scaling Divide (P‑40.2). If you want to just divide the value, set this to 1.000 and adjust P‑40.2 accordingly. This function is disabled if this parameter is set to 0. | ||||||
P-40.2 | Display Scaling Divide | 1.000 | 100.000 | 1.000 | - | |
P-41 | PI Controller Proportional Gain | 0.0 | 30.0 | 1.0 | - | |
P-42 | PI Controller Integral Time | 0.0 | 30.0 | 1.0 | s | |
P-43.0 | PI Operation | 0 | 1 | 0 | - | |
| ||||||
P-43.1 | PI Mode | 0 | 1 | 0 | - | |
| ||||||
P-43.2 | PI Wake Mode | 0 | 1 | 0 | - | |
| ||||||
P-44 | PI Reference (Setpoint) Source Select | 0 | 2 | 0 | - | |
| ||||||
P-45 | PI Fixed Reference | P-46.2 | P-46.3 | 0.0 | - | |
P-46.0 | PI Feedback Source | 0 | 5 | 0 | - | |
| ||||||
P-46.1 | PI Feedback Function | 0 | 1 | 0 | - | |
| ||||||
P-46.2 | PI Feedback Sensor Minimum Signal | -1000.0 | P-46.3 | 0.0 | - | |
P-46.3 | PI Feedback Sensor Maximum Signal | P-46.2 | 1000.0 | 100.0 | - | |
P-46.2 and P-46.3 are used together to define the connected sensor range for PI operation, so that all PI related parameters can be set in Engineering units. Example : If you have a sensor that measures 2‑10 bar. Enter 2.0 in P‑46.2 and 10.0 P46.3. | ||||||
Tip
For more information on PI operaton > PI Operation