Skip to main content

E4 Help Desk

P-35 Analogue Input 1 & Master Follower Scaling

Analogue Input 1 & Master Follower Scaling

Par.

Description

Minimum

Maximum

Default

Units

P-35.0

DA4 Minimum V / mA

0.0

20.0

0.0

V/mA

P-35.1

DA4 Maximum V / mA

0.0

20.0

10.0

V/mA

P-35.2

DA4 Minimum Speed

-P-01

P-01

0.00

Hz/RPM

P-35.3

DA4 Maximum Speed

-P-01

P-01

50.00

Hz/RPM

The above parameters are active when Analog Input 1 Format (P‑16.0) is set to scaled voltage or scaled current and are used to scale and offset the connected signal.

Example : 2-8VDC signal, where 2V is 0Hz and 8V is 40Hz.

Set : P-16.0 = U Scal, P-35.0 = 2.0V, P-35.1 = 8.0V, P-35.2 = 0.00Hz, P-35.3 = 40.00Hz.

P-35.4

Master Follower Speed Scaling

0.0

2000.0

100.0

%

When operating in Master Follower Mode (P-12.0 = 7), the operating speed of the drive will be the Master speed multiplied by this factor, limited by the minimum and maximum speeds.

Tip

For more information on DA4 setup > Using a Voltage signal to control Motor Speed

For more information on Master Follower > Master Follower Operation