Par.

Description

Units

P0-00

Keypad Parameter Display Mode

-

This parameter allows the user to see only the parameters that have been set different to defaults.

0: Show all Parameters. (Note: The setting of parameter P-14 limits the parameter groups which are shown).

1: Show Only parameters that are different from Factory defaults.

2: Show Only parameters that are different from User defaults.

P0-01

Digital Input 1 to 4 Status

-

Displays the status of the Drive Digital Input Terminals 1 to 4.

Display Value

0

0

0

0

Input Terminal

DI1 Status

DI2 Status

DA3 Status

DA4 Status

1 = Input Active

0 = Input InActive

P0-03

STO Input Status

-

Displays the status of the Safe Torque Inputs.

P0-03 Value

ST1/ST2 Input State

0

Open

1

Closed

P0-04

Relay Status

-

Displays the status of Relay 1.

P0-04 Value

NO Contact with respect to C

NC Contact with respect to C

0

Open

Closed

1

Closed

Open

P0-06

Digital Output Status

-

Displays the status of the Drive Digital Output AD1.

P0-06 Value

AD1 Digital Output Status

000

Off

100

On

P0-07

Analog Output 1 Value

V / mA

Shows the voltage/Current output value from Analog output 1(DA1) after Scaling and Offsets have been applied.

P-25.0 (DA1 Output 1 Type)

P-25.4 (DA1 Format)

P0-07 (Display Value)

0 (Digital Output)

N/A

0.0 (Output Off)

N/A

1.0 (Output On)

1 (Analog Output)

U 0-10, U 10-0

Value in Volts

A 0-20, A 20-0, A 4-20, A 20-4

Value in mA

P0-09

Analog Input 1 Applied Signal Level

V/mA

Displays the actual signal level applied to Analog Input 1 (DA3) before Scaling and Offsets have been applied.

P0-10

Analog Input 1 Final Signal Level

%

Displays the signal level after Offset and Scaling (P-35) is applied.

P0-11

Analog Input 2 Applied Signal Level

V/mA

Displays the actual Signal Level applied to Analog Input 2 (DA4) before Scaling and Offsets have been applied.

P0-12

Analog Input 2 Final Signal Level

%

Displays the Signal Level after Offset and Scaling (P-35) is applied.

P0-13

Pre-Ramp Speed Controller Reference

Hz/Rpm

Displays the set point reference input applied to the Drive internal speed controller.

P0-14

Speed Reference via Fieldbus Network

Hz/Rpm

Displays the setpoint being received by the Drive from the currently active Fieldbus interface.

P0-15

Post-Ramp Speed Controller Reference

Hz/Rpm

Displays the Post-Ramp Set-Point Reference applied to the Drive internal speed controller.

P0-16

Speed Error

Hz/Rpm

Speed Error between the Post-Ramp Speed Controller Reference (P0-15) and the Rotor speed (P0-18).

P0-17

User PI Output

-

P0-17.0

User PI Output

P0-17.1

User PI Reference Value

P0-17.2

User PI Feedback Value

P0-18

Rotor Speed

Hz/Rpm

This parameter displays the estimated Rotor Speed of the Motor.

P0-21

Calculated Slip Speed Value (Enhanced V/F Mode Only)

Hz/Rpm

Displays the Calculated Slip Speed.

P0-22

Measured Motor Power Factor

Cos Phi

Real time Motor Power Factor whilst drive is running.

P0-23

Highest Current During Acceleration

A

Records the Highest Current during the Acceleration Ramp. Stored value is the Highest Current from the previous run.

P0-24

Highest Current During Deceleration

A

Records the Highest Current during the Deceleration Ramp. Stored value is the Highest Current from the previous run.

P0-25

Motor Current

A

Real time Motor Current.

P0-26

Motor Magnetising Current (Id)

A

Displays the Motor Magnetising Current, providing an Auto-tune has been successfully completed.

P0-27

Motor Rotor Current (Iq)

A

Displays the Motor Rotor (torque producing) Current, providing an Auto-tune has been successfully completed.

P0-28

Output Torque

%

Displays the instantaneous Output Torque level produced by the Motor.

0.1% resolution 100% = motor rated torque.

P0-29

Motor Input Power

kW

P0-30

Motor Shaft Power

kW

P0-31

Motor Overload Accumulator

%

P0-32

Back EMF Measured Value

VAC

Ph-Ph Back EMF measurement.

P0-33

Drive Output Voltage

VAC

Displays the Instantaneous Output Voltage from the Drive to the Motor.

P0-34

Motor Poles (Calculated)

PP

Displays the calculated number of Pole Pairs.

P0-35

Power Stage State

-

Displays what the Drive is currently doing at any time.

P0-36

Power Stage State at Trip

-

P0-37

Currently Active Trip Code

-

This parameter indicates the current Trip Code.

P0-38

Trip History Log

-

Displays the last four Fault Codes.

P0-38.0

Last Trip 1 (Newest Trip)

P0-38.1

Last Trip 2

P0-38.2

Last Trip 3

P0-38.3

Last Trip 4 (Oldest Trip)

P0-39

Last Trip Time (Newest)

-

P0-39.0

Last Trip 1 (Newest Trip)

P0-39.1

Last Trip 2

P0-39.2

Last Trip 3

P0-39.3

Last Trip 4 (Oldest Trip)

P0-40

DC Bus Voltage

Vdc

Displays the Instantaneous DC Bus Voltage internally within the Drive.

P0-41

DC Bus Voltage Ripple

Vdc

Displays the level of Ripple present on the DC Bus Voltage.

P0-42

L1 Input Voltage

VAC

Measured Input Voltage on Terminal L1.

P0-43

L2 Input Voltage

VAC

Measured Input Voltage on Terminal L2.

P0-44

L3 Input Voltage

VAC

Measured Input Voltage on Terminal L3.

P0-45

Motor Thermistor Resistance

ohms

Measured Analog Input 1 Thermistor Resistance.

P0-46

Motor Thermistor 2 Resistance

ohms

Measured Analog Input 2 Thermistor Resistance.

P0-47

Brake Resistor Active

-

0 = Brake Resistor Off.

1 = Brake Resistor On.

P0-48

IGBT Temperature

°C

Displays the Instantaneous Heatsink (IGBT thermistor) Temperature measured by the drive.

P0-49

Drive Internal Temperature

°C

Displays the Instantaneous Internal (Control PCB) Temperature measured by the drive.

P0-50

Drive Run Time Since Last Trip

-

Displays the Running Time of the Drive since the last trip occurred.

P0-50.0

Hours Running Since Last Trip

P0-50.1

Seconds Running Since Last Trip

P0-52

Drive Run Time Since Last Enable

-

Displays the Total Running Time of the Drive since the last Run command was received.

P0-52.0

Hours Running Since Last Enable

P0-52.1

Seconds Running Since Last Enable

P0-53

Drive Lifetime Operating Time

-

Displays the total Operating Time of the Drive. The first value shown is the number of hours. Pressing the Up key will display the seconds.

P0-53.0

Drive Operating time (Hours)

P0-53.1

Drive Operating time (s)

P0-54

Drive Total Run Time

-

Displays the Total Run Time of the drive. The first value shown is the number of hours. Pressing the Up key will display the seconds.

P0-54.0

Drive Total Run Time (Hours)

P0-54.1

Drive Total Run Time (s)

P0-55

Drive Heatsink Cooling Fan Total Operating Time

-

Displays the total operating time of the Drive internal cooling fans. The first value shown is the number of hours. Pressing the Up key will display the minutes and seconds. This is used for scheduled maintenance information.

P0-55.0

Drive Heatsink Cooling Fan Total Run Time (Hours)

P0-55.1

Drive Heatsink Cooling Fan Total Run Time (s)

P0-56

Fire Mode

-

P0-56.0

Hours in Fire Mode

P0-56.1

Seconds in Fire Mode

P0-56.2

Hours When Fire Started

P0-56.3

Seconds When Fire Started

P0-56.4

Fire Mode Counter

P0-57

Time Remaining to Next Service

-

The time remaining to the Next Service.

P0-58

STO Deactivation Counter

-

STO Deactivation Counter.

Counts up 1 each time the STO inputs see a falling edge (Drive powered from mains).

P0-64

Actual Switching Frequency

kHz

P0-70

Drive Type

-

Displays the Type details of the drive.

P0-70.0

Drive Rated Voltage (V)

P0-70.1

Drive Rated Current (A)

P0-70.2

Drive Frame Size

P0-70.3

Drive Rated Power (kW)

P0-70.4

Drive Rated Power (HP)

P0-70.5

Number of Input Phases

P0-70.6

Drive Type Code

P0-72

Drive IO Firmware Version

-

P0-72.0

IO Firmware Version

P0-72.1

IO Firmware Checksum

P0-72.2

IO Personality Version

P0-73

Drive Power Stage Firmware Version

-

P0-73.0

Power Stage Firmware Version

P0-73.1

Power Stage Firmware Checksum

P0-74

Drive Serial Number

-

Displays the unique Serial Number of the Drive.

P0-74.0

Serial Number (High)

P0-74.1

Serial Number (Low)

P0-75

PS Read Value

-

Internal use only.