Advanced Motor Control

Par.

Description

Minimum

Maximum

Default

Units

P-50

Motor Power Factor

0.00

0.99

Drive Dependant

-

P-51

Motor Control Mode

0

7

1

-

0: IM Smart Vector Speed Control

1: V/F Speed Control

2: PM Vector Speed Control

3: BLDC Vector Speed Control

4: SynRel Vector Speed Control

5: LSPM Vector Speed Control

6: Permanent Magnet-assisted Synchronous Reluctance

7: IM Full Vector Speed Control

P-52

Motor Autotune

0

1

0

-

0: Disabled

1: Enabled

P-53.0

Vector Speed P-Gain

0.0

400.0

50.0

%

P-53.1

Vector Speed I-Gain

0

1000

50

ms

P-53.2

Speed Feedback Filter Time

0

1000

0

ms

P-53.3

Current Loop P-Gain

0.0

400.0

0.0

%

P-53.4

Current Loop I-Gain

0.0

400.0

0.0

%

P-54.0

Maximum Current Limit

0.0

175

150

%

P-54.1

O-I Current Maximum

0.0

Rating Dependant

Rating Dependant

-

P-55.0

Motor Stator Resistance

0.000

44.250

Rating Dependant

Ohms

P-55.1

Motor Rotor Resistance

0.000

44.250

Rating Dependant

Ohms

P-56.0

Motor Stator inductance (Lsd)

0.0

6553.5

Rating Dependant

mH

P-56.1

Motor Magnetising Current (Id rms)

0.0

Rating Dependant

Rating Dependant

A

P-57

Motor Stator q-axis Inductance (Lsq)

0.0

6553.5

Rating Dependant

mH

Tip

For more information on the motor control modes > Commissioning an Induction Motor