Skip to main content

E4 Help Desk

P-58 DA3 Analog Input 2 Setup

DA3 Analog Input 2 Setup

Par.

Description

Minimum

Maximum

Default

Units

P-58.0

DA3 Minimum V / mA

0.0

20.0

0.0

V/mA

P-58.1

DA3 Maximum V / mA

0.0

20.0

10.0

V/mA

P-58.2

DA3 Minimum Speed

-P-01

P-01

0.00

Hz/RPM

P-58.3

DA3 Maximum Speed

-P-01

P-01

50.00

Hz/RPM

The above parameters are active when Analog Input 2 Format (P‑47.0) is set to scaled voltage or scaled current and are used to scale and offset the connected signal.

Example : 2-8VDC signal, where 2V is 0Hz and 8V is 40Hz.

Set : P-47.0 = U Scal, P-58.0 = 2.0V, P-58.1 = 8.0V, P-58.2 = 0.00Hz, P-58.3 = 40.00Hz.

Tip

For more information on DA3 setup > Using a Voltage signal to control Motor Speed