P-58 DA3 Analog Input 2 Setup
DA3 Analog Input 2 Setup
Par. | Description | Minimum | Maximum | Default | Units |
|---|---|---|---|---|---|
P-58.0 | DA3 Minimum V / mA | 0.0 | 20.0 | 0.0 | V/mA |
P-58.1 | DA3 Maximum V / mA | 0.0 | 20.0 | 10.0 | V/mA |
P-58.2 | DA3 Minimum Speed | -P-01 | P-01 | 0.00 | Hz/RPM |
P-58.3 | DA3 Maximum Speed | -P-01 | P-01 | 50.00 | Hz/RPM |
The above parameters are active when Analog Input 2 Format (P‑47.0) is set to scaled voltage or scaled current and are used to scale and offset the connected signal. Example : 2-8VDC signal, where 2V is 0Hz and 8V is 40Hz. Set : P-47.0 = U Scal, P-58.0 = 2.0V, P-58.1 = 8.0V, P-58.2 = 0.00Hz, P-58.3 = 40.00Hz. | |||||
Tip
For more information on DA3 setup > Using a Voltage signal to control Motor Speed