CANopen Service Data Objects

CANopen - Service Data Objects (SDO)

All user adjustable parameters are accessible through the CAN communication interface using Service Data Objects (SDO)

The operation of SDOs is on the basis of client/server relationship. The client sends requests and the server responds to those requests.

SDO Functions

SDO message may be used for the following functions:

  • Read a parameter value

  • Write to a parameter

SDO COB-ID

By default, SDO messages have the following COB-ID's:

  • Client to server message has the COB-ID 600h + node ID

  • Server to client response will have the COB-ID 580h + node ID

The node ID is the value set in Parameter P2-07 CANopen Address.

SDO Message Format

SDO messages have the following format:

Byte 0

Byte 1

Byte 2

Byte 3

Byte 4

Byte 5

Byte 6

Byte 7

Control Byte

Index (16 Bit)

Sub Index (8 Bit)

Data (Up to 32 Bits)

See Control Byte Section

LSB

MSB

SDO Control Byte

The following values for the SDO Control Byte are supported:

Control Byte

Function

0x40

Read Request (Any Size Data)

0x4F

Read Request - Single Byte

0x4B

Read Request - Single Word

0x43

Read Request - Double Word

0x2F

Write Request - Single Byte

0x2B

Write Request - Single Word

0x23

Write Request - Double Word

0x60

Write Response - Successful

0x80

Write Response - Unsuccessful

The following are examples of using the SDO to read or write data.

Example 1 - Client request the value of Index 1018h Sub Index 1 (Vendor ID) from server with node-ID = 1

SDO Message: Client to Server:

COB-ID

Control Byte

Index

Sub Index

Data

0x601

0x40

0x18

0x10

0x0

Not Required

Note

COB-ID of the request = 0x600 + node ID so for node ID= 1, 0x601

The Index value is transferred with MSB first

The expected response would be:

COB-ID

Control Byte

Index

Sub Index

Data

0x581

0x4B

0x18

0x10

0x0

Data Value (Single Word)

Note

The COB-ID of the response telegram is 0x580 + Node-ID so for Node-ID = 1, the value is 0x581

The Control Byte will indicate the data length, in this example a single word value

Example 2 - Client attempts to write the value of Index 1018h Sub Index 1 (Vendor ID) from server with node-ID = 1

In this case, the message from the Client to the server becomes:

COB-ID

Control Byte

Index

Sub Index

Data

0x601

0x2B

0x18

0x10

0x0

e.g. 0x0001

The Vendor ID value will be read only and therefore the Server should reject the request as follows:

COB-ID

Control Byte

Index

Sub Index

Data

0x581

80

0x18

0x10

0x0

0x06010002

The server will respond with an error code, see the Section SDO Error Code Responses for details on the error codes.

If an error occurs, for instance an entry does not exist, the device returns a message containing a completion code that represents the error.

The following table lists some of the common error code response that may be received.

Data Value

Meaning

0x05040000

SDO Timeout

0x05040001

Invalid Control Byte

0x06010002

Write Access attempted to a Read Only value

0x0602000

SDO Object does not exist

0x06040041

The referenced object cannot be mapped to a PDO

0x06020042

The size or number of mapped objects results in an invalid PDO size

0x06070010

Data type or length is not compatible

0x06090011

SDO Sub Index does not exist

0x06090031

Parameter value too low

0x06090032

Parameter value too high