UPS Overview

Functional differences in Rescue Mode with a UPS Supply

During Rescue Mode operation some features are disabled/altered. Below is a list of drive features that are different in Rescue Mode with a UPS Supply to normal mains supply operation.

Function

Rescue Mode

Input Phase Loss Detection

Disabled

DC Bus Ripple detection

Disabled

Undervoltage trip levels

Reduced - Exact Values

Speed Selection - Group 8

No longer active

Speeds in Group 7 are used (P7-02 and P7-09) depending on the Rescue Operation Function selected in parameter P7-02

Speed Loop Gains - Group 9

No longer active

Rescue Mode has its own dedicated gains in (P7-06 and P7-07)

Motor Auto-tune

Disabled

Starting the Drive

To run the drive in Rescue Mode the following terminals must be closed:

  • Safe Torque Off Terminals STO1 & STO2

  • Direction function Digital Input (normally DI1 or DI2)

DC Injection at Start/Stop

Disabled