Skip to main content

Elevator Core Reference Guide

Group 1 Parameter Descriptions

Group 1.1 - User IO - Primary Command Source Selection

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-01

Primary Command Source

N/A

0: Terminal

0: Terminal

1: Modbus RTU

2: CANopen

3: Reserved

RW

N

N/A

1

2065h

0

101

Select the command source for the drive.

Setting

Drive Display

Function

0 : Terminal

tEr

The drive responds directly to control signals applied to the drive control terminals.

Terminal designations assigned with parameter P1-02.

1 : Modbus RTU

rtu

The drive only responds to Modbus RTU commands sent to the RJ45 port on the drive.

2 : CANopen

CAn

The drive only responds to CAN bus commands sent to the RJ45 port on the drive.

3: Reserved

-

Reserved

Note

When using either Modbus RTU or CANopen no Digital Input needs to be closed (High) for the drive to run.

However the drive will not start unless the Safe Torque Off terminals STO1 and STO2 are closed.

Safety_Chain_Wiring.svg

Group 1.2 - User IO - Control Terminal Function Select

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-02

Control Terminal Function Select

N/A

1: Macro 1

0: Macro 0

1: Macro 1

2: Macro 2

3: Macro 3

4: Macro 4

5: Macro 5

6: Macro 6

7: Macro 7

8: Macro 8

9: Macro 9

10: Macro 10

11: Macro 11

12: Macro 12

RW

N

N/A

1

2066h

0

102

This parameter provides a terminal macro system to pre-define how each control terminal operates. Select the one most appropriate to the elevator control and feedback signals that your system has.

If set to 0 the terminal designations are freed off in parameter Group 12 (made read/write) to allow the user to define their own terminal functions using Parameters P12-01 to P12-10.

For details on each Macro see the Macro Table below.

When the Primary Command Source (P1-01) is set to 0, the setting of Parameter P1-02 defines the function of each of the drives control terminals.

Use the Macro table below to select an appropriate value of P1-02 to match the elevator controller output signals.

The status of the control terminals can be monitored using parameter P0-01 and P0-02.

P0-01 Display value

0

0

0

0

0

Function

Digital Input 1 status

Digital Input 2 status

Digital Input 3 status

Digital Input 4 status

Digital Input 5 status

P0-02 Display value

0

0

0

0

0

Function

Digital Input 6 status

Digital Input 7 status

Digital Input 8 status

Daux 1 Input status

Daux 2 Input status

The Macro tables are used by P1-02 to select the function of each IO Input. P1-02 parameter can be found here.Group 1 User IO - Parameter List

Table 1. Macro Settings

P1-02 Setting

DI1

DI2

DI3

DI4

DI5

DI6

Speed Source

DI7

DI8

0

User Configurable using Group 12

1

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

Open = Disabled

Closed = Levelling Speed (P8-05)

Open = Disabled

Closed = High Speed (P8-06)

Open = Disabled

Closed = High Speed 5/Relevelling Speed (P8-12)

Open = Disabled

Closed = Inspection Speed (P8-08)

If more than 1 speed selection input is high the largest speed value will be used.

Fault Reset

Open = Mains Mode

Closed = Rescue Mode Activate

2

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

Open = Disabled

Closed = Levelling Speed (P8-05)

Open = Disabled

Closed = High Speed (P8-06)

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

  • Brake Resistor monitoring trip if P3- 06 is set to 1.

Closed = Ok

Open = Disabled

Closed = Inspection Speed (P8-08)

Open = Mains Mode

Closed = Rescue Mode Activate

Fault Reset

For settings 1 and 2 above, the drive will only start if all the below conditions are met:

  1. Safe Torque off inputs are enabled (P0-03 = 1)

  2. A direction Command (DI1 or DI2) has been given.

  3. At least 1 speed has been selected.

3

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

1

0

0

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

Closed = Ok

P8-06 High Speed

Fault Reset

Open = Mains Mode

Closed = Rescue Mode Activate

0 or 1

0

1

P8-07 Intermediate Speed

0 or 1

1

0 or 1

P8-08 Inspection Speed

0

0

0

P8-05 Levelling Speed

4

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

1

0

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

  • Brake Resistor monitoring trip if P3- 06 is set to 1.

Closed = Ok

0

P8-06 High Speed

Fault Reset

Open = Mains Mode

Closed = Rescue Mode Activate

0 or 1

0

1

P8-07 Intermediate Speed

0 or 1

1

0 or 1

P8-08 Inspection Speed

0

0

0

P8-05 Levelling Speed

5

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

0

0

0

No Function

P8-05 Levelling Speed

Fault Reset

Open = Mains Mode

Closed = Rescue Mode Activate

1

0

0

P8-06 High Speed

0

1

0

P8-07 Intermediate Speed

1

1

0

P8-08 Inspection Speed

0

0

1

P8-09 Speed 2

1

0

1

P8-10 Speed 3

0

1

1

P8-11 Speed 4

1

1

1

P8-12 High Speed 5/Relevelling Speed

6

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

No Function

Speed Reference from Analogue input

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

  • Brake Resistor monitoring trip if P3- 06 is set to 1.

Closed = Ok

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

Closed = Ok

Analog input Reference level

Fault Reset

Open = Mains Mode

Closed = Rescue Mode Activate

7

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

Open = Disabled

Closed = Levelling Speed (P8-05)

Torque Sensor Input

Open = Disabled

Closed = High Speed (P8-06)

Open = Disabled

Closed = Inspection Speed (P8-08)

If more than 1 speed selection input is high the highest speed will be used.

Fault Reset

Open = Mains Mode

Closed = Rescue Mode Activate

For settings 3,4,5,6,7 above, the drive will only start if all the below conditions are met and in the correct sequence

  1. Safe Torque Off inputs are enabled.

  2. A direction command (DI1 or DI2) has been given.

  3. At least 1 speed has been selected (For Macros 3,4 and 5)

8

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

0

0

Brake Release Monitor Input 1

(Only Active if P5-04 Brake Release Monitoring Enable is set to a value of 2)

Brake Release Monitor Input 2

(Only Active if P5-04 Brake Release Monitoring Enable is set to a value of 2)

P8-05 Levelling Speed

Fault Reset

Open = Mains Mode

Closed = Rescue Mode Activate

1

0

P8-06 High Speed

0

1

P8-07 Intermediate Speed

1

1

P8-08 Inspection Speed

For setting 8 above, the drive will only start if all the below conditions are met and in the correct sequence.

  1. Safe Torque Off inputs are enabled.

  2. A direction command (DI1 or DI2) has been given.

*9

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

Open = Mains Mode

Closed = Rescue Mode Activate

0

0

0

P8-05 Levelling Speed

Brake Release Monitor Input 1

(Only Active if P5-04 Brake Release Monitoring Enable is set to a value of 2)

Open = Disabled

Closed = Drive Enabled

1

0

0

P8-06 High Speed

0

1

0

P8-07 Intermediate Speed

1

1

0

P8-08 Inspection Speed

0

0

1

P8-09 Speed 2

1

0

1

P8-10 Speed 3

0

1

1

P8-11 Speed 4

1

1

1

P8-12 High Speed 5/Relevelling Speed

*Setting 9 above has a different operation (in terms of Motor contactor control) to all other operating modes.

When a direction command is given the motor contactor relay will close and normal contactor sequence will begin, however the drive will not start until STO inputs are closed and then Digital Input 8 (Drive Enable signal) has been given.

10

Open = Disabled

Open = Disabled

Open = Disabled

Closed = Run Reverse

0

0

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

Closed = Ok

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

Closed = Ok

P8-05 Levelling Speed

Open Available Functions =

  • E-Trip when open with no other functions enabled

  • Brake Resistor monitoring trip if P3- 06 is set to 1.

Closed = Ok

Open = Mains Mode

Closed = Rescue Mode Activate

1

0

P8-06 High Speed

0

1

P8-07 Intermediate Speed

1

1

P8-08 Inspection Speed

*11

Open = Disabled

Open = Run Forward

Open = Disabled

Closed = Run Reverse

Open = Mains Mode

Closed = Rescue Mode Activate

0

0

0

P8-05 Levelling Speed

Brake Release Monitor Input 1

(Only Active if P5-04 Brake Release Monitoring Enable is set to a value of 2)

No Function

1

0

0

P8-06 High Speed

0

1

0

P8-07 Intermediate Speed

1

1

0

P8-08 Inspection Speed

0

0

1

P8-09 Speed 2

1

0

1

P8-10 Speed 3

0

1

1

P8-11 Speed 4

1

1

1

P8-12 High Speed 5/Relevelling Speed

*Setting 11 above has a different operation (in terms of Motor contactor control) to all other operating modes:

When a direction command is given the motor contactor relay will close and normal contactor sequence will begin, however the drive will not start until STO inputs are closed.

12

Open = Disabled

Closed = Run Forward

Open = Disabled

Closed = Run Reverse

1

0

Open = Coast to Stop

Closed = No Action

No Function

P8-06 High Speed

Fault Reset

Open = Mains Mode

Closed = Rescue Mode

0 or 1

1

P8-08 = Inspection Speed

0

0

P8-05 = Levelling Speed



Motor Contactor Sequence

The table below defines for each macro setting what signals are required at the drive terminals to close the motor contactor and in what sequence as shown in (x)

Macro Number (P1-02)

Safe Torque Off signals

Direction Signal

Speed Source Signal

Motor Contactor state (As driven by Relay 1)

1,2,3,4,5,6,7,8,10,12

On (1st)

On (2nd)

On (3rd)

Closed

9,11

On/Off

On

On/Off

Closed (Driven By Direction Signal only)

Group 1.3 - User IO - Analog Input 1 (DI4) configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-03

DI4 Analog Input 1 Format

N/A

0: U 0-10

0 ... 9

RW

N

N/A

1

2067h

0

103

P1-04

DI4 Analog Input 1 Offset

%

0.0%

-500.0 ... 500.0%

RW

Y

1 = 0.1%

2

2068h

0

104

P1-05

DI4 Analog Input 1 Scaling

%

100.0%

-500.0 ... 500.0%

RW

Y

1 = 0.1%

2

2069h

0

105

P1-06

DI4 Analog Input 1 Filter

sec

0.00s

0.00 ... 2.00s

RW

Y

1 = 0.01s

1

206Ah

0

106

P1-07

DI4 Analog Input Signal Loss Reaction

N/A

0: No Reaction

0 ... 2

RW

Y

N/A

1

206Bh

0

107

P1-08

DI4/DI5 Analog Input Signal Loss Speed

%

80.00%

0.00 ... 100.00%

RW

Y

1 = 0.01%

1

206Ch

0

108

Select the configuration for Analog Input 1. Digital Input 4 only operates as an Analog Input when P1-02 is set to 6 or 7 or configured via Group 12 when using Macro 0.

Setting

Drive Display

Input Format

U 0-10

U 0-10

0 to 10 Volt Signal (Uni-polar

U 10-0

U 10-0

10 to 0 Volt Signal (Uni-polar)

-10 - 10

- 10- 10

-10 to +10 Volt Signal (Bi-polar)

A 0-20

A 0-20

0 to 20mA Signal

A 20-4

A 20-0

20 to 0mA Signal

t 4-20

A 4-20

4 to 20mA Signal (4-20F trip if signal falls below 3mA)

t 20-4

A 20-4

20 to 4mA Signal (20-4F trip if signal falls below 3mA)

PrE-t

PrE-t

Pre-Torque Input (Bipolar -10V to +10V)

Ptc-th

Ptc-th

Motor PTC thermistor input

tY-th

ty-th

Motor KTY84 thermistor input

When Terminal DI4 is operating as an Analog Input this parameter allows an offset to be set, the value is set as a percentage of the full-scale range of the input, which is applied to the Analog Input signal.

When Terminal DI4 is operating as an Analog Input this parameter scales the Analog Input by this factor, e.g. if P1-03 is set for U 0–10, and the scaling factor is set to 200.0%, a 5 Volt input at the control terminal DI4 will result in the drive running at maximum speed (P8-01).

The pre and post scaling values can be viewed in parameters P0-56 and P0-57.

This filter helps in situations where the Analog Input is used for the speed reference or from a Torque sensor and the source signal is noisy which would result in oscillation in speed.

The filters primary aim is to make the signal smoother to the internal speed reference but will result in less responsiveness.

Set the reaction when the Analog Input signal is lost, when terminal DI4 is used as Analog Input speed reference. Speed reference loss is defined as the point when the speed reference falls below a % (as per set in P1-07) of the previous reference for a period of 500ms.

Setting

Reaction

0

No Reaction

1

Run at speed in P1-08 (Analog Input Signal Loss speed) and return to the original speed reference when the signal is reinstated.

2

Ramp to Stop using P8-04 (Deceleration ramp time) and trip Ai-LoS

Used in conjunction with P1-07 (DI4/DI5 Analog Input Signal Loss Reaction) and P1-13 (Analog Input 2) Signal Loss Reaction setting 1 and is set as a % of the speed reference prior to the speed reference loss.

Group 1.4 User IO - Analog Input 2 (DI5) configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-09

DI5 Analog Input 2 Format

N/A

0: U 0-10

0 ... 9

RW

Y

N/A

1

206Dh

0

109

P1-10

DI5 Analog Input 2 Offset

%

0.0%

-500.0 ... 500.0%

RW

Y

1 = 0.1%

2

206Eh

0

110

P1-11

DI5 Analog Input 2 Scaling

%

100.0%

-500.0 ... 500.0%

RW

Y

1 = 0.1%

2

206Fh

0

111

P1-12

DI5 Analog Input 2 Filter

sec

0.00s

0.00 ... 2.00s

RW

Y

1 = 0.01s

1

2070h

0

112

P1-13

DI5 Analog Input 2 Signal Loss Reaction

N/A

0: No Reaction

0 ... 2

RW

Y

N/A

1

2071h

0

113

Below are the analog configurations available for Analog Input 2.

Setting

Drive Display

Input Format

U 0-10

U 0-10

0 to 10 Volt Signal (Uni-polar

U 10-0

U 10-0

10 to 0 Volt Signal (Uni-polar)

-10 - 10

- 10- 10

-10 to +10 Volt Signal (Bi-polar)

A 0-20

A 0-20

0 to 20mA Signal

A 20-4

A 20-0

20 to 0mA Signal

t 4-20

A 4-20

4 to 20mA Signal (4-20F trip if signal falls below 3mA)

t 20-4

A 20-4

20 to 4mA Signal (20-4F trip if signal falls below 3mA)

PrE-t

PrE-t

Pre-Torque Input (Bipolar -10V to +10V)

Ptc-th

Ptc-th

Motor PTC thermistor input

tY-th

ty-th

Motor KTY84 thermistor input

When Terminal DI5 is operating as an Analog Input this parameter allows an offset to be set, the value is set as a percentage of the full-scale range of the input, which is applied to the Analog Input signal.

When Terminal DI5 is operating as an Analog Input scales the Analog Input by this factor, e.g. if P1-09 is set for U 0–10, and the scaling factor is set to 200.0%, a 5 Volt input at the control terminal DI5 will result in the drive running at Maximum Speed (P8-01).

The pre and post scaling values can be viewed in parameters P0-58 and P0-59.

This filter helps in situations where the Analog Input is used for the speed reference or from a Torque sensor and the source signal is noisy which would result in oscillation in speed.

The filters primary aim is to make the signal smoother to the internal speed reference but will result in less responsiveness.

Set the reaction when the Analog Input signal is lost, when terminal DI5 is used as Analog Input speed reference. Speed reference loss is defined as the point when the speed reference falls below a % (as per set in P1-07) of the previous reference for a period of 500ms.

Setting

Reaction

0

No Reaction

1

Run at speed in P1-08 (Analog Input Signal Loss speed) flashing Ai-LoS and return to speed reference when signal is reinstated.

2

Ramp to Stop using P8-04 (Deceleration ramp time) and trip Ai-LoS or F-Ptc or F-tY depending on P1-09 setting.

Group 1.5 - User IO - DA1 Output 1 Configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-14

DA1 Output 1 Type

N/A

0: Digital Output

0 ... 1

RW

Y

N/A

1

2072h

0

114

P1-15

DA1 Digital Output 1 Function Select

N/A

1: Drive Healthy

0 ... 20

RW

Y

N/A

1

2073h

0

115

P1-16

DA1 Digital Output 1 Invert

N/A

0: Standard

0: Standard

1: Inverted

RW

Y

N/A

1

2074h

0

116

P1-17

DA1 Analog Output 1 Source Select

N/A

0 : Output Frequency

0 ... 5

RW

Y

N/A

1

2075h

0

117

P1-18

DA1 Analog Output 1 Format

N/A

0: U 0-10

0 ... 5

RW

Y

N/A

1

2076h

0

118

P1-19

DA1 Analog Output 1 Scaling

%

100.0%

0.0 ... 500.0 %

RW

Y

1 = 0.1%

1

2077h

0

119

P1-20

DA1 Analog Output 1 Offset

%

0.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

2078h

0

120

Sets if the output terminal DA1 is to operate as a Digital Output (24Vdc) or as an Analog Output. In analog mode, the type of Analog Output (voltage/current) is defined by P1-18 Analog Output 1 Format and the data source is given by P1-17. In digital mode, the output is controlled by P1-15.

Setting

DA1 Output Type

0

Digital Output

1

Analog Output

This defines the output function when terminal DA1 is configured in digital mode (P1-14 = 0).

Setting

Status/Function Source

Conditions for Status

0

Drive Enabled (Running)

Logic 1 when Drive is enabled and output stage is on

1

Drive Healthy

Logic 1 when no Fault condition exists on the drive. (“InHibit” is not included as a fault)

2

Motor Below Minimum Speed

Logic 1 when motor speed is </=minimum output frequency (P8-02) or </= DC injection at stop speed (P9-15)

3

Motor at Target Speed

Logic 1 when the output frequency matches the setpoint speed

4

Motor Speed > 0

Logic 1 when the motor runs above zero speed

5

Motor Speed ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as set in P1-31 and P1-32

6

Motor Current ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as set in P1-31 and P1-32

7

Motor Torque ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as set in P1-31 and P1-32

8

STO Status

Logic 1 when both STO inputs are present, and the drive is able to be operated

9

Rescue Mode Active

Logic 1 when the drive is operating in Rescue Mode

10

2nd Anip > limit

Logic 1 when the signal applied to terminal DI5 (Analog Input 2) exceeds the adjustable limits set in speed P1-31 and P1-32

Note

When using settings 5, 6, 7, 10, parameters P1-31 and P1-32 must be used together to control the behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in P1-31 and return to Logic 0 when the signal falls below the value in P1-32.

11

Motor Contactor control

Used to control the operation of a motor contactor. Logic 1 when motor contactor is closed by the drive.

12

Motor Shorting Contactor Control

Used to control the operation of a motor shorting contactor.

13

Direction of Travel

Logic 1 when direction down, Logic 0 when stopped or direction up.

(Fwd command given and speed is positive):

Up direction means a forward command has been given and motor turns clockwise (Looking at the shaft) and motor speed is positive.

14

Service Indicator

Logic 1 when service time interval set in P11-17 has been met.

15

Brake Control

Logic 1 when Relay is closed (Motor Brake Released)

16

Door Zone

Logic 1 when motor speed equals (P10-02 Early Door Opening Speed Threshold).

17

Light Load direction

Logic 0 = Easiest direction is up.

Logic 1 = Easiest direction is downwards.

18

Travel limit counter reached

Logic 1 when Travel Direction Change Counter limit P10-05 has been reached.

19

Set speed and actual speed > P1-42

Logic 1 when the % difference (as set in Speed following error P1-42) is exceeded between set speed and the actual speed (estimated speed in open loop/encoder speed in closed loop-with encoder)

20

Alarm

Logic 1 when an alarm is active, e.g P3-07 has been set to 2.

Inverts the logic of DA1 output when operating in digital output mode (P1-14 = 0).

Setting

Function

0

Standard

1

Inverted

This defines the output source when DA1 is configured in analog mode.

Setting

Status Source

Signal Source

0

Output Frequency (Motor Speed) -Estimated

0 to P8-01 (Maximum Frequency)

1

Output (Motor) current

0 to 200% of P4-03

2

Motor Torque

0 to 200% of motor rated torque

3

Electrical Output power

0 to 200% of drive rated power

4

Output Speed From Encoder

0 to 200% of P8-01 (Maximum Frequency)

5

DC Bus voltage

0 to 1000Vdc

Sets the format for DA1 when in Analog Mode selected by P1-14.

Setting

Output Format

U 0-10

0 to 10V

U 10-0

10 to 0V

A 0-20

0 to 20mA

A 20-0

20 to 0mA

A 4-20

4 to 20mA

A 20-4

20 to 4mA

Defines the scaling percentage of DA1.

Defines the scaling factor as a %, where output value = (Input value-Offset P1-20) *Scaling factor P1-19

Group 1.6 - User IO - DA2 Output 2 configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-21

DA2 Output 2 Type

N/A

0: Digital Output

0 ... 1

RW

Y

N/A

1

2079h

0

121

P1-22

DA2 Digital Output 2 Function Select

N/A

0: Drive Enabled (Running)

0 ... 20

RW

Y

N/A

1

207Ah

0

122

P1-23

DA2 Digital Output 2 Invert

N/A

0: Standard

0: Standard

1: Inverted

RW

Y

N/A

1

207Bh

0

123

P1-24

DA2 Analog Output 2 Source Select

N/A

0: Output Frequency

0 ... 5

RW

Y

N/A

1

207Ch

0

124

P1-25

DA2 Analog Output 2 Format

N/A

0: U 0-10

0 ... 5

RW

Y

N/A

1

207Dh

0

125

P1-26

DA2 Analog Output 2 Scaling

%

100.0%

0.0 ... 500.0 %

RW

Y

1 = 0.1%

2

207Eh

0

126

P1-27

DA2 Analog Output 2 Offset

%

0.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

207Fh

0

127

Sets if the output from terminal DA2 is to operate as a Digital Output (24V dc) or as an Analog Output, the Analog type is defined in P1-25 DA2 Analog Output 2 Format.

Setting

Output Type

0

Digital Output

1

Analog Output

Selects the function of the DA2 output when configured in digital mode.

Setting

Status/Function Source

Conditions for Status

0

Drive Enabled (Running)

Logic 1 when Drive is enabled and output stage is on

1

Drive Healthy

Logic 1 when no Fault condition exists on the drive. (“InHibit” is not included as a fault)

2

Motor Below Minimum Speed

Logic 1 when motor speed is </=minimum output frequency (P8-02) or </= DC injection at stop speed (P9-15)

3

Motor at Target Speed

Logic 1 when the output frequency matches the setpoint speed

4

Motor Speed > 0

Logic 1 when the motor runs above zero speed

5

Motor Speed ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-33 and P1-34

6

Motor Current ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-33 and P1-34

7

Motor Torque ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-33 and P1-34

8

STO Status

Logic 1 when both STO inputs are present, and the drive is able to be operated

9

Rescue Mode Active

Logic 1 when the drive is operating in Rescue Mode

10

2nd Anip > limit

Logic 1 when the signal applied to terminal DI5 (Analog Input 2) exceeds the adjustable limits set in speed P1-33 and P1-34

Note

When using settings 5, 6, 7, 10, parameters P1-33 and P1-34 must be used together to control the behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in P1-33 and return to Logic 0 when the signal falls below the value in P1-34.

11

Motor Contactor control

Used to control the operation of a motor contactor. Logic 1 when motor contactor is closed by the drive.

12

Motor Shorting Contactor Control

Used to control the operation of a motor shorting contactor.

13

Direction of Travel

Logic 1 when direction down, Logic 0 when stopped or direction up.

(Fwd command given and speed is positive):

Up direction means a forward command has been given and motor turns clockwise (Looking at the shaft) and motor speed is positive.

14

Service Indicator

Logic 1 when service time interval set in P11-17 has been met.

15

Brake Control

Logic 1 when Relay is closed (Motor Brake Released)

16

Door Zone

Logic 1 when motor speed equals (P10-02 Early Door Opening Speed Threshold).

17

Light Load direction

Logic 0 = Easiest direction is up.

Logic 1 = Easiest direction is downwards.

18

Travel limit counter reached

Logic 1 when Travel Direction Change Counter limit P10-05 has been reached.

19

Set speed and actual speed > P1-42

Logic 1 when the % difference (as set in Speed following error P1-42) is exceeded between set speed and the actual speed (estimated speed in open loop/encoder speed in closed loop-with encoder)

20

Alarm

Logic 1 when an alarm is active, e.g P3-07 has been set to 2.

Inverts the logic of DA2 output when operating in digital output mode.

Setting

Function

0

Standard

1

Inverted

This defines the output source when DA2 is configured in analog mode.

Setting

Status Source

Signal Source

0

Output Frequency (Motor Speed) -Estimated

0 to P8-01 (Maximum Frequency)

1

Output (Motor) current

0 to 200% of P4-03

2

Motor Torque

0 to 200% of motor rated torque

3

Electrical Output power

0 to 200% of drive rated power

4

Output Speed From Encoder

0 to 200% of P8-01 (Maximum speed rpm)

5

DC Bus voltage

0 to 1000Vdc

Defines the format of Analog Output 2

Setting

Output Format

U 0-10

0 to 10V

U 10-0

10 to 0V

A 0-20

0 to 20mA

A 20-0

20 to 0mA

A 4-20

4 to 20mA

A 20-4

20 to 4mA

Inverts the logic of DA2 output when operating in digital output mode.

Defines the scaling factor as a %, where output value = (Input value-Offset P1-27)*Scaling factor P1-26.

Group 1.7 - User IO - Digital Output 3 Configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-28

DO3 Digital Output 3 Function Select

N/A

12: Motor Shorting Contactor

0 ... 20

RW

Y

N/A

1

2080h

0

128

P1-29

DO3 Digital Output 3 Invert

N/A

0: Standard

0: Standard

1: Inverted

RW

Y

N/A

1

2081h

0

129

The settings of the DO3 terminal are listed below:

Setting

Status/Function Source

Conditions for Status

0

Drive Enabled (Running)

Logic 1 when Drive is enabled and output stage is on

1

Drive Healthy

Logic 1 when no Fault condition exists on the drive. (“InHibit” is not included as a fault)

2

Motor Below Minimum Speed

Logic 1 when motor speed is </=minimum output frequency (P8-02) or </= DC injection at stop speed (P9-15)

3

Motor at Target Speed

Logic 1 when the output frequency matches the setpoint speed

4

Motor Speed > 0

Logic 1 when the motor runs above zero speed

5

Motor Speed ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-38 and P1-39

6

Motor Current ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-38 and P1-39

7

Motor Torque ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-38 and P1-39

8

STO Status

Logic 1 when both STO inputs are present, and the drive is able to be operated

9

Rescue Mode Active

Logic 1 when the drive is operating in Rescue Mode

10

2nd Anip > limit

Logic 1 when the signal applied to terminal DI5 (Analog Input 2) exceeds the adjustable limits set in speed P1-38 and P1-39

Note

When using settings 5, 6, 7, 10, parameters P1-38 and P1-39 must be used together to control the behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in P1-38 and return to Logic 0 when the signal falls below the value in P1-39.

11

Motor Contactor control

Used to control the operation of a motor contactor. Logic 1 when motor contactor is closed by the drive.

12

Motor Shorting Contactor Control

Contactor control

Used to control the operation of a motor shorting contactor.

13

Direction of Travel

Logic 1 when direction down, Logic 0 when stopped or direction up.

(Fwd command given and speed is positive):

Up direction means a forward command has been given and motor turns clockwise (Looking at the shaft) and motor speed is positive.

14

Service Indicator

Logic 1 when service time interval set in P11-17 has been met.

15

Brake Control

Logic 1 when Relay is closed (Motor Brake Released)

16

Door Zone

Logic 1 when motor speed equals (P10-02 Early Door Opening Speed Threshold).

17

Light Load direction

Logic 0 = Easiest direction is up.

Logic 1 = Easiest direction is downwards.

18

Travel limit counter reached

Logic 1 when Travel Direction Change Counter limit P10-05 has been reached.

19

Set speed and actual speed > P1-42

Logic 1 when the % difference (as set in Speed following error P1-42) is exceeded between set speed and the actual speed (estimated speed in open loop/encoder speed in closed loop-with encoder)

20

Alarm

Logic 1 when an alarm is active, e.g P3-07 has been set to 2.

Inverts the logic of DO3 output terminal.

Setting

Function

0

Standard

1

Inverted

Group 1.8 - User IO - User Relays

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-30

Relay 1 Function Select

N/A

11: Motor Contactor Control

0 ... 20

RW

Y

N/A

1

2082h

0

130

The settings of Relay 1 are listed below.

Setting

Status/Function Source

Conditions for Status

0

Drive Enabled (Running)

Logic 1 when Drive is enabled and output stage is on

1

Drive Healthy

Logic 1 when no Fault condition exists on the drive. (“InHibit” is not included as a fault)

2

Motor Below Minimum Speed

Logic 1 when motor speed is </=minimum output frequency (P8-02) or </= DC injection at stop speed (P9-15)

3

Motor at Target Speed

Logic 1 when the output frequency matches the setpoint speed

4

Motor Speed > 0

Logic 1 when the motor runs above zero speed

5

Motor Speed ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-35 and P1-36

6

Motor Current ≥ Limit

Logic 1 when the motor current exceeds the adjustable limit as per set in P1-35 and P1-36

7

Motor Torque ≥ Limit

Logic when the motor torque exceeds the adjustable limit as per set in P1-35 and P1-36

8

STO Status

Logic 1 when both STO inputs are present, and the drive is able to be operated

9

Rescue Mode Active

Logic 1 when the drive is operating in Rescue Mode

10

2nd Anip > limit

Logic 1 when the signal applied to terminal DI5 (Analog Input 2) exceeds the adjustable limit as per set in P1-35 and P1-36

Note

When using settings 5, 6, 7, 10, parameters P1-35 and P1-36 must be used together to control the behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in P1-35 and return to Logic 0 when the signal falls below the value in P1-36.

11

Motor Contactor control

Used to control the operation of a motor contactor. Logic 1 when motor contactor is closed by the drive.

12

Motor Shorting Contactor Control

Contactor control

Used to control the operation of a motor shorting contactor.

13

Direction of Travel

Logic 1 when direction down, Logic 0 when stopped or direction up.

(Fwd command given and speed is positive):

Up direction means a forward command has been given and motor turns clockwise (Looking at the shaft) and motor speed is positive.

14

Service Indicator

Logic 1 when service time interval set in P11-17 has been met.

15

Brake Control

Logic 1 when Relay is closed (Motor Brake Released)

16

Door Zone

Logic 1 when motor speed equals (P10-02 Early Door Opening Speed Threshold).

17

Light Load direction

Logic 0 = Easiest direction is up.

Logic 1 = Easiest direction is downwards.

18

Travel limit counter reached

Logic 1 when Travel Direction Change Counter limit P10-05 has been reached.

19

Set speed and actual speed > P1-42

Logic 1 when the % difference (as set in Speed following error P1-42) is exceeded between set speed and the actual speed (estimated speed in open loop/encoder speed in closed loop-with encoder)

20

Alarm

Logic 1 when an alarm is active, e.g P3-07 has been set to 2.

Group 1.9 - User IO - Hysteresis

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-31

DA1 Threshold Upper Limit

%

100.0%

P1-32 ... 200.0 %

RW

Y

1 = 0.1%

1

2083h

0

131

P1-32

DA1 Threshold Lower Limit

%

0.0%

0.0 ... P1-31

RW

Y

1 = 0.1%

1

2084h

0

132

P1-33

DA2 Threshold Upper Limit

%

100.0%

P1-34 ... 200.0 %

RW

Y

1 = 0.1%

1

2085h

0

133

P1-34

DA2 Threshold Lower Limit

%

0.0%

0.0 ... P1-33

RW

Y

1 = 0.1%

1

2086h

0

134

P1-35

Relay 1 Threshold Upper Limit

%

100.0%

0.0 ... 200.0 %

RW

Y

1 = 0.1%

1

2087h

0

135

P1-36

Relay 1 Threshold Lower Limit

%

0.0%

0.0 ... 100.0 %

RW

Y

1 = 0.1%

1

2088h

0

136

P1-37

Digital/Relay Output Hysteresis Band

%

0.3%

0.0 ... 25.0 %

RW

Y

1 = 0.1%

1

2089h

0

137

P1-38

DO3 Threshold Upper Limit

%

100.0%

0.0 ... 200.0%

RW

Y

1 = 0.1%

1

208Ah

0

138

P1-39

DO3 Threshold Lower Limit

%

0.0%

0.0 ... 100.0%

RW

Y

1 = 0.1%

1

208Bh

0

139

Used in conjunction with settings 5,6,7,10 of Parameter P1-15 (DA1 Digital Output Function Select).

The table below shows the specific settings of P1-15 and the parameter that P1-31/P1-32 look at for the % to change the state of the Digital Output.

Setting

Status/Function Setting

Parameter monitored for Relay State Change

4

Motor Speed > 0

P0-15 Post-ramp Speed Controller Reference

5

Motor Speed ≥ Limit

P0-15 Post-ramp Speed Controller Reference

6

Motor Current ≥ Limit

P0-25 Motor Current

7

Motor Torque ≥ Limit

P0-28 Output Torque

Used in conjunction with settings 5,6,7,10 of Parameter P1-15 DA1 Digital Output 1 Function Select to set the lower limit of Digital Output 1.

Used in conjunction with settings 5,6,7,10 of Parameter P1-22 (DA2 Digital Output Function Select).

The table below shows the specific settings of P1-22 and the parameter that P1-31/P1-32 look at for the % to change the state of the Digital Output.

Setting

Status/Function Setting

Parameter monitored for Relay State Change

4

Motor Speed > 0

P0-15 Post-ramp Speed Controller Reference

5

Motor Speed ≥ Limit

P0-15 Post-ramp Speed Controller Reference

6

Motor Current ≥ Limit

P0-25 Motor Current

7

Motor Torque ≥ Limit

P0-28 Output Torque

Used in conjunction with settings 5,6,7,10 of Parameter P1-22 DA1 Digital Output 2 Function Select to set the lower threshold of Digital Output 2.

Used in conjunction with settings 5,6,7,10 of Parameter P1-30 (Relay 1 Source Selector)

The table below shows the settings of P1-30 and the parameter that P1-35/P1-36 look at for the % to change the state of the Relay.

Setting

Status/Function Setting

Parameter monitored for Relay State Change

4

Motor Speed > 0

P0-15 Post-ramp Speed Controller Reference

5

Motor Speed ≥ Limit

P0-15 Post-ramp Speed Controller Reference

6

Motor Current ≥ Limit

P0-25 Motor Current

7

Motor Torque ≥ Limit

P0-28 Output Torque

Used in conjunction with settings 5,6,7,10 of Parameter P1-30 (Relay 1 Source Selector) to set the lower threshold of Relay 1.

This parameter works in conjunction with P1-15, P1-22, P1-28, P1-30 = 2 or 3 to set a band around the Motor at Target Speed (e.g. P1-15 = 3) or Motor at Zero speed (e.g. P1-15 = 2). When the speed is within this band, the drive is considered to be at Target speed or Zero speed. This function is used to prevent “chatter” on the relay/Digital output if the operating speed coincides with the level at which the digital / relay output changes state. e.g. if P1-30 = 3, P8-01 = 50Hz and P1-36 = 5%, the relay contacts close above 2.5Hz.

Used in conjunction with settings 5,6,7,10 of Parameter P1-28 DO3 Digital Output 3 Function Select to set the upper limit of the threshold.

Used in conjunction with settings 5,6,7,10 of Parameter P1-28 DO3 Digital Output 3 Function Select

Group 1.9 - User IO - Logic Control

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-40

Start Mode Select / Automatic Restart

N/A

0: Edge-r

0 ... 6

RW

Y

N/A

1

208Ch

0

140

P1-41

Auto-reset delay time

sec

20s

1 ... 60s

RW

Y

N/A

1

208Dh

0

141

P1-42

Speed Following Error

%

5.0%

0.0 ... 50.0%

RW

Y

1 = 0.1%

2

208Eh

0

142

P1-43

Positive/Negative Logic Select

N/A

0: Positive Logic

0: Positive Logic

1: Negative Logic

RW

N

N/A

1

208Fh

0

143

Defines the behaviour of the drive relating to the Direction / Enable Digital Input and configures the Automatic Restart function.

Setting

Behaviour

Edge-r

Following power on or reset, the drive will not start if a Direction Input remains closed. The Input must be closed after a power on or reset to start the drive.

Auto-0

Following a power on or Reset, the drive will automatically start if the start conditions are met, without the need to seeing a rising edge.

Auto-1 to Auto-5

Following a power on or Reset, the drive will automatically start if the start conditions are met, without the need to seeing a rising edge.

Also following a trip, the drive will make up to 5 attempts to restart at 20 second intervals. The drive must be powered down to reset the counter. The number of restart attempts are counted, and if the drive fails to start on the final attempt, the drive will display a fault message, and will require the user to manually reset the fault.

Note

The default reset time is 20 seconds and can be modified using parameter P1-41.

Sets the delay time which will elapse between consecutive drive reset attempts when Auto Reset is enabled in P1-40.

Note

This parameter is only applicable if the other run conditions are fulfilled. For example even if P1-40 is set to Auto-1 and the direction input is closed the drive will not start if the Safety Chain is not closed.

Used in conjunction with Setting 19: Set speed and actual speed > P1-42 in parameters P1‑15, P1‑22, P1‑28 and P1‑30 as the % error difference between set speed and the actual speed.

Setting

Status/Function Source

Conditions for Status

19

Set speed and actual speed > P1-42

Logic 1 when the % difference (as set in Speed following error P1-42) is exceeded between set speed and the actual speed (estimated speed in open loop/encoder speed in closed loop-with encoder)

Changes the control logic for all Digital Inputs (including the Universal Encoder module terminals Daux1 and Daux2).

Setting

Logic

0

Positive Logic

1

Negative Logic

Note

STO1 and STO2 Inputs are always positive logic.