Group 2 Parameter Descriptions

Group 2.1 - Communications - Modbus RTU

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P2-01

Modbus Slave Address

N/A

1

0 ... 247

RW

N

N/A

1

20C9h

0

201

P2-02

Modbus RTU Baud Rate

N/A

4: 115200bps

0: 9600bps

1: 19200bps

2: 38400bps

3: 57600bps

4: 115200bps

RW

N

N/A

1

20CAh

0

202

P2-03

Modbus RTU Data Format

N/A

0: n-1

0: n-1

1: n-2

2: 0-1

3: E-1

RW

N

N/A

1

20CBh

0

203

P2-04

Modbus Communications Loss Timeout

sec

1.0s

0.0 ... 5.0s

RW

N

1 = 0.1s

1

20CCh

0

204

P2-05

Communications Loss Action

N/A

0: Trip

0: Trip

1: Ramp to Stop the Trip

2: Ramp to Stop Only (No Trip)

3: Run at Inspection Speed (P8-08)

RW

Y

N/A

1

20CDh

0

205

P2-06

Modbus RTU Response Delay

N/A

0 char

0 ... 16 char

RW

N

N/A

1

20CEh

0

206

Sets the drive address when communicating over Modbus RTU via the RJ45 port on the drive.

Sets the baud rate when Modbus RTU communications is being used.

Value

Setting

Format

0

n-1

No Parity, 1 stop bit

1

n-2

No parity, 2 stop bits

2

0-1

Odd parity, 1 stop bit

3

E-1

Even parity, 1 stop bit

Sets the timeframe for a Modbus message to be sent to the drive before tripping.

Controls the behaviour of the drive following a loss of communications from either Modbus RTU or CANopen.

Setting

Drive Display

Reaction

0

triP

Immediate trip

1

r-triP

Ramp to stop then trip

2

StoP

Ramp to stop only (No Trip)

3

InSPct

Run at Inspection Speed (P8-08)

Allows the user to configure an additional delay between the drive receiving a request via the Modbus RTU interface and transmitting a reply. The value entered represents the delay in addition to the minimum delay permissible according to the Modbus RTU specification, and is expressed as the number of additional characters.

Group 2.2 - Communications - CANopen

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P2-07

CANopen Address

N/A

1

1 ... 127

RW

N

N/A

1

20CFh

0

207

P2-08

CANopen Baud Rate

N/A

2: 500kbps

0: 125kbps

1: 250kbps

2: 500kbps

3: 1Mbps

RW

N

N/A

1

20D0h

0

208

P2-09

CANopen Communication Loss Reaction

N/A

2: Ramp to Stop Only (No Trip)

0: Trip

1: Ramp to Stop then Trip

2: Ramp to Stop Only (No Trip)

3: Run at Inspection Speed (P8-09)

 RW

Y

N/A 

1

20D1h

0

209

Specifies the node ID of this device on the CANopen network. Set to 0 to disable the CANopen port.

Sets the baud rate when CANopen communications is being used.

Controls the behaviour of the drive following a loss of communications with a CANopen device while using Heartbeat or Node Guarding.

Setting

Reaction

0

Immediate trip

1

Ramp to stop then trip

2

Ramp to stop only (No Trip)

3

Run at Inspection Speed (P8-08)

Group 2.3 - Communications - USB-C

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P2-10

PC/App Communications Loss Timeout

sec

2.0s

0.0 ... 5.0s

RW

N

1 = 0.1s

1

20D2h

0

210

P2-11

PC/App Communications Loss Action

N/A

0: Trip

0: Trip

1: Ramp to Stop then Trip

2: Ramp to Stop Only (No Trip)

3: Run at Inspection Speed (P8-09)

RW

N

N/A

1

20D3h

0

211

P2-13

USB Port Enable

N/A

1: Enabled

0: Disabled

1: Enabled

RW

Y

N/A

1

20D5h

0

213

Sets the timeframe for a PC/App message to be sent to the drive before tripping.

Controls the behaviour of the drive following a loss of communications from either PC Tool/Mobile App.

Setting

Drive Display

Reaction

0

triP

Immediate trip

1

r-triP

Ramp to stop then trip

2

StoP

Ramp to stop only (No Trip)

3

InSPct

Run at Inspection Speed (P8-08)

Determines whether the USB port on the drive is enabled or not.

If the USB port is disabled then the drive will show the message USB P on the drive display, indicating that the USB port is disabled.

Setting

Function

0

Disabled - Messages can not be transferred via USB to the drive.

1

Enabled - Messages can be transferred via USB to the drive.

Group 2.4 - Communications - Modbus Message Monitoring

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P2-20

Modbus Messages Per Second

msg/s

0

0 ... 1000msg/s

RO

N

N/A

2

20DCh

0

220

P2-21

Modbus Messages Processed

N/A

0

0 ... 4294967295

RO

N

N/A

4

20DDh

0

221

P2-22

Modbus Errors

N/A

0

0 ... 4294967295

RO

N

N/A

4

20Deh

0

222

Number of Modbus RTU messages currently being processed per second.

Total number of Modbus RTU messages processed.

Number of Modbus RTU messages that could not be processed due to errors.

Group 2.5 - Communications - USB-C Message Monitoring

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P2-23

USB Messages Processed Per Second

msg/s

0

0 ... 1000ms

RO

N

N/A

2

20DFh

0

223

P2-24

USB Messages Processed

N/A

0

0 ... 4294967295

RO

N

N/A

4

20E0h

0

224

P2-25

USB Errors

N/A

0

0 ... 4294967295

RO

N

N/A

4

20E1h

0

225

The number of messages currently being processed per second.

Total number of messages processed from the USB port.

The number of messages from the USB port that failed to be processed.

Group 2.6 - Communications - Modbus Drive Monitoring

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P2-50

Modbus Control Word

N/A

0

0 ... 7

RO

N

N/A

1

20FAh

0

250

P2-51

Modbus Speed Reference

Hz

0.00

-P8-01 ... P8-01

RO

Y

N/A

2

20FBh

0

251

P2-52

Modbus Torque Reference

%

0.0

0.0 ... 100.0%

RO

Y

1 = 0.1%

2

20FCh

0

252

P2-53

Modbus Ramp Rate

sec

0.0

0.0 ... 600.0

RO

Y

1 - 0.1s

2

20FDh

0

253

P2-56

Modbus Status Word Lower Byte: Drive Status

N/A

0

0 ... 255

RO

N

N/A

2

2100h

0

256

P2-56 (1)

Modbus Status Word Upper Byte: Error Code

N/A

0

0 ... 255

RO

N

N/A

2

2100h

1

256

P2-57

Modbus Speed Feedback

Hz / rpm / Linear

0.00

-P8-01 ... P8-01

RO

N

1 = 0.1Hz

2

2101h

0

257

P2-58

Modbus Motor Current

Amps

0.0A

-3276.7 ... 3276.7A

RO

N

1 = 0.1A

2

2102h

0

258

P2-59

Modbus Output Torque

%

0.0%

-200.0 ... 200.0%

RO

N

1 = 0.1%

2

2103h

0

259

Allows the user to monitor the Control word individual bits

The drive Control Word is as follows:

Bit

Function when Bit = 0

Function When Bit = 1

0

No Function

Drive Run Forward

1

No Function

Drive Run Reverse

2

No Function

Reset Fault

Displays the speed reference received via Modbus.

Displays the torque reference received via Modbus

Displays the ramp rate received via Modbus.

Shows the real-time Modbus status word lower byte.

The below table shows the lower bytes individual bits

Bit

Function when Bit = 0

Function When Bit = 1

0

Drive Stopped

Drive Running

1

Drive Healthy

Drive Tripped

2

STO Closed

STO Open (Drive Inhibited)

3

Service Time not Reached

Service Time Reached

4

Drive not in Standby

Drive in Standby

5

Reserved

Reserved

6

Reserved

Reserved

7

Reserved

Shows the real-time Modbus status word upper byte.

Speed feedback from Modbus command.

Only active while P1-01 is set to rtu

Motor Current feedback while using Modbus.

Only active while P1-01 is set to rtu

Output Torque feedback while using Modbus.

Only active while P1-01 is set to rtu