Group 5.1 - Motor Brake Control - Motor Brake Control

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P5-01

Brake Release Time

sec

0.5s

0.0 ... 5.0s

RW

Y

1 = 0.1s

1

21F5h

0

501

P5-02

Brake Apply Delay

sec

0.2s

0.0 ... 5.0s

RW

Y

1 = 0.1s

1

21F6h

0

502

P5-03

Brake Apply Speed

Hz / rpm / Linear

0.00

0.00 ... P8-01

RW

Y

1 = 0.01Hz

2

21F7h

0

503

Sets the delay time, in which it takes for the motor brake to be released (Relay 2 or Function) before the drive output frequency ramps up.

This value should bet set so there is enough time for the motor brake to be released (this time can be found from the manufacture's datasheet).

Sets the delay time, for the motor brake to apply (Relay 2 to open).

Sets the speed at which the drive will open Relay 2 and apply the motor brake.

If P5-03 has a value > 0 then DC Injection at Stop (P9-13) is not active in Geared Induction open loop control (P4-01 = 0 or 1).

Group 5.2 - Motor Brake Control - Motor Brake Monitoring

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P5-04

Brake Release Monitoring Enable

N/A

0: Function Off

0 ... 2

RW

Y

N/A

1

21F8h

0

504

P5-05

Brake Release Monitoring Time

sec

0.5s

0.1 ... 5.0s

RW

Y

1 = 0.1s

1

21F9h

0

505

P5-06

Brake Release Number of Errors Before Lockout

N/A

0

0 ... 5

RW

Y

N/A

1

21FAh

0

506

P5-07

Brake Release Monitoring Errors

N/A

0

0 ... 65535

RO

N

N/A

2

21FBh

0

507

Setting

Function

0 (Function Disabled)

Motor Brake Release Monitoring Disabled

1

Motor Brake Release Monitoring Enabled and monitored via Daux 1 Input and Daux 2 Input on the Universal Encoder Module with 2 N/C contacts.

2

Motor Brake Release Monitoring Enabled and monitored via Digital Inputs DI5 and DI6 providing that P1-02 is set to Macro 8 and Digital input DI7 if P1-02 is set to 9.

If the monitoring terminal has not changed state in this time (since the brake has been released by relay 2 of the drive) then the drive will trip "bF-Err" or "bF-Loc" (if number of attempts as set in P5-06 has been met)

The drive will automatically try to clear the "bF-Err" at 1.5 second intervals for the number of times set, after each attempt the travel sequence will restart, once the number of brake release monitoring errors has reached the number set in this parameter a permanent trip "bF-Loc" will be displayed.

Total number of "bF-Err" trips since the drive was installed.

The counter can be reset when default the drive parameters.

Group 5.3 - Motor Brake Control - Alternative Motor Brake Control

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P5-08

Brake Release Speed

Hz / rpm / Linear

0.00 

0.00 ... 10.00Hz

RW

Y

1 = 0.01

2

21FCh

0

508

P5-09

Brake Release Torque

%

0.0%

0.0 ... 100.0%

RW

Y

1 = 0.1%

2

21FDh

0

509

P5-08 - Brake Release Speed

Set this to the speed at which you want the Motor Brake to be released. Once P5-08 & P5-09 values have been met the brake will be released.

This parameter is only active if P5-01 is set to 0 & both P5-08 & P5-09 have a value > 0.

P5-09 - Brake Release Torque

Set this to the torque value at which you want the Motor Brake to be released. Once P5-08 & P5-09 values have been met the brake will be released.

This parameter is only active if P5-01 is set to 0 & both P5-08 & P5-09 have a value > 0.