Elevator Core Reference Guide

Relay Output 1

Relay Output 1 is a freely programmable relay output on the drive. The Relay supports both Normally Open or Normally Closed configuration.

Relay

AC Supply

DC Supply

Relay 1

N/C = 5A/250VAC

N/O = 6A/250VAC

N/C = 5A/30VDC

N/O = 6A/30VDC

The diagram below illustrates the available settings for Relay 1.

Features_and_Functions_-_Control_Terminals_-_Relay_Output_1_-_Overview.svg

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-30

Relay 1 Function Select

N/A

11: Motor Contactor Control

0 ... 20

RW

Y

N/A

1

2082h

0

130

P1-35

Relay 1 Threshold Upper Limit

%

100.0%

0.0 ... 200.0 %

RW

Y

1 = 0.1%

1

2087h

0

135

P1-36

Relay 1 Threshold Lower Limit

%

0.0%

0.0 ... 100.0 %

RW

Y

1 = 0.1%

1

2088h

0

136

P1-37

Digital/Relay Output Hysteresis Band

%

0.3%

0.0 ... 25.0 %

RW

Y

1 = 0.1%

1

2089h

0

137

The settings of Relay 1 are listed below.

Setting

Status/Function Source

Conditions for Status

0

Drive Enabled (Running)

Logic 1 when Drive is enabled and output stage is on

1

Drive Healthy

Logic 1 when no Fault condition exists on the drive. (“InHibit” is not included as a fault)

2

Motor Below Minimum Speed

Logic 1 when motor speed is </=minimum output frequency (P8-02) or </= DC injection at stop speed (P9-15)

3

Motor at Target Speed

Logic 1 when the output frequency matches the setpoint speed

4

Motor Speed > 0

Logic 1 when the motor runs above zero speed

5

Motor Speed ≥ Limit

Logic 1 when the motor speed exceeds the adjustable limit as per set in P1-35 and P1-36

6

Motor Current ≥ Limit

Logic 1 when the motor current exceeds the adjustable limit as per set in P1-35 and P1-36

7

Motor Torque ≥ Limit

Logic when the motor torque exceeds the adjustable limit as per set in P1-35 and P1-36

8

STO Status

Logic 1 when both STO inputs are present, and the drive is able to be operated

9

Rescue Mode Active

Logic 1 when the drive is operating in Rescue Mode

10

2nd Anip > limit

Logic 1 when the signal applied to terminal DI5 (Analog Input 2) exceeds the adjustable limit as per set in P1-35 and P1-36

Note

When using settings 5, 6, 7, 10, parameters P1-35 and P1-36 must be used together to control the behaviour. The output will switch to Logic 1 when the selected signal exceeds the value programmed in P1-35 and return to Logic 0 when the signal falls below the value in P1-36.

11

Motor Contactor control

Used to control the operation of a motor contactor. Logic 1 when motor contactor is closed by the drive.

12

Motor Shorting Contactor Control

Contactor control

Used to control the operation of a motor shorting contactor.

13

Direction of Travel

Logic 1 when direction down, Logic 0 when stopped or direction up.

(Fwd command given and speed is positive):

Up direction means a forward command has been given and motor turns clockwise (Looking at the shaft) and motor speed is positive.

14

Service Indicator

Logic 1 when service time interval set in P11-17 has been met.

15

Brake Control

Logic 1 when Relay is closed (Motor Brake Released)

16

Door Zone

Logic 1 when motor speed equals (P10-02 Early Door Opening Speed Threshold).

17

Light Load direction

Logic 0 = Easiest direction is up.

Logic 1 = Easiest direction is downwards.

18

Travel limit counter reached

Logic 1 when Travel Direction Change Counter limit P10-05 has been reached.

19

Set speed and actual speed > P1-42

Logic 1 when the % difference (as set in Speed following error P1-42) is exceeded between set speed and the actual speed (estimated speed in open loop/encoder speed in closed loop-with encoder)

20

Alarm

Logic 1 when an alarm is active, e.g P3-07 has been set to 2.

Used in conjunction with settings 5,6,7,10 of Parameter P1-30 (Relay 1 Source Selector)

The table below shows the settings of P1-30 and the parameter that P1-35/P1-36 look at for the % to change the state of the Relay.

Setting

Status/Function Setting

Parameter monitored for Relay State Change

4

Motor Speed > 0

P0-15 Post-ramp Speed Controller Reference

5

Motor Speed ≥ Limit

P0-15 Post-ramp Speed Controller Reference

6

Motor Current ≥ Limit

P0-25 Motor Current

7

Motor Torque ≥ Limit

P0-28 Output Torque

Used in conjunction with settings 5,6,7,10 of Parameter P1-30 (Relay 1 Source Selector) to set the lower threshold of Relay 1.

This parameter works in conjunction with P1-15, P1-22, P1-28, P1-30 = 2 or 3 to set a band around the Motor at Target Speed (e.g. P1-15 = 3) or Motor at Zero speed (e.g. P1-15 = 2). When the speed is within this band, the drive is considered to be at Target speed or Zero speed. This function is used to prevent “chatter” on the relay/Digital output if the operating speed coincides with the level at which the digital / relay output changes state. e.g. if P1-30 = 3, P8-01 = 50Hz and P1-36 = 5%, the relay contacts close above 2.5Hz.