Motor Contactor Control Setup Wiring

Normally the motor contactor is connected to Relay 1 on the drive. By default Relay 1 is set to control the motor contactor.

When connecting your motor contactor to the drive ensure you are using the correct terminals.

Features_and_Functions_-_Motor_Contactor_-_Contactor_Setup_-_Relay_Terminals.svg

Relay 1 supports both an Normally Open (NO) and Normally Closed (NC) configuration.

The ratings for Relay 1 are listed below:

Relay

AC Supply

DC Supply

Relay 1

N/C = 5A/250VAC

N/O = 6A/250VAC

N/C = 5A/30VDC

N/O = 6A/30VDC

Motor Contactor Control Setup Parameters

For the drive to control the motor contactor it must be correctly connected to the drive, details of the connections can be found in the TopicMotor Contactor Control Setup Wiring.

Once the motor contactor is connected the drive must be correctly parameterised.

Motor Contactor Control Function Parameters

Normally the motor contactor is connected to Relay 1 as the Relay can provide 250VAC/30Vdc to drive the motor contactor. Though the 3 other Digital Outputs may be used.

Below are the parameters that need to be set so an Output can control the motor contactor:

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-15

DA1 Digital Output 1 Function Select

N/A

1: Drive Healthy

0 ... 20

RW

Y

N/A

1

2073h

0

115

P1-22

DA2 Digital Output 2 Function Select

N/A

0: Drive Enabled (Running)

0 ... 20

RW

Y

N/A

1

207Ah

0

122

P1-28

DO3 Digital Output 3 Function Select

N/A

12: Motor Shorting Contactor

0 ... 20

RW

Y

N/A

1

2080h

0

128

P1-30

Relay 1 Function Select

N/A

11: Motor Contactor Control

0 ... 20

RW

Y

N/A

1

2082h

0

130

Motor Contactor Control Delay Time Parameters

When a run command is given to the drive the first step before running is for the motor contactors to close. This time can be adjusted in Parameter P3-01 to give sufficent time for the motor contactors to fully close.

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P3-01

Motor Contactor Closing Time

sec

0.2s

0.0 ... 5.0s

RW

Y

1 = 0.1s

1

212Dh

0

301