Group 12 Parameter Descriptions

Group 12.1 - User I/O Configuration - Input Function Select

Parameter Number

Parameter Name

Units

Default

Available Settings

Drop Down Options

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P12-01

DI1 Input Function select

N/A

1: Run Forward

0 ... 29

0: No Function

1: Run Forward

2: Run Reverse

3: Levelling Speed

4: High Speed

5: High Speed 5

6: Inspection Speed

7: Fault Reset

8: Rescue Mode

9: E-Trip Mode 1

10: Preset with override High Speed 

11: Preset with override Inspection Speed

12: Preset with override Intermediate Speed

13: E-Trip Mode 2 

14: Preset Bit 0 (2)

15: Preset Bit 1 (2) 

16: Preset Bit 2 (2)

17: Speed Reference 

18: Torque Sensor 

19: Forward, Contactor Control

20: Reverse, Contactor Control

21: Drive Enable

22: E-Trip Mode 3

23: Brake Release Monitor Input 1

24: Brake Release Monitor Input 2 

25: Analog mode 

26: Direction (0 – Fwd, 1 - Rev)

27: Preset Bit 0 With Active (3) 

28: Preset Bit 1 With Active (3)

29: Preset Bit 2 With Active (3)

RW

Y

N/A

1

24B1h

0

1201

P12-02

DI2 Input Function select

N/A

2: Run Reverse

0 ... 29

RW

Y

N/A

1

24B2h

0

1202

P12-03

DI3 Input Function select

N/A

3: Levelling Speed

0 ... 29

RW

Y

N/A

1

24B3h

0

1203

P12-04

DI4 Input Function select

N/A

4: High Speed

0 ... 29

RW

Y

N/A

1

24B4h

0

1204

P12-05

DI5 Input Function select

N/A

5: High Speed 5

0 ... 29

RW

Y

N/A

1

24B5h

0

1205

P12-06

DI6 Input Function select

N/A

6: Inspection Speed

0 ... 29

RW

Y

N/A

1

24B6h

0

1206

P12-07

DI7 Input Function select

N/A

7: Fault Reset

0 ... 29

RW

Y

N/A

1

24B7h

0

1207

P12-08

DI8 Input Function select

N/A

8: Rescue Mode

0 ... 29

RW

Y

N/A

1

24B8h

0

1208

P12-09

Daux1 Input Function select

N/A

0: No Function

0 ... 29

RW

Y

N/A

1

24B9h

0

1209

P12-10

Daux2 Input Function select

N/A

0: No Function

0 ... 29

RW

Y

N/A

1

24BAh

0

1210

When P1-02 = 0 these eight parameters are used to select the Function of each digital input terminal (DI1 to DI8) on the drive from the table below:

Drop Down Options

Function

Open

Closed

0: No Function

Input Disabled

Input Disabled

1: Run Forward

Disabled

Run Forward

2: Run Reverse

Disabled

Run Reverse

3: Levelling Speed

Disabled

Run at Levelling Speed (P8-05)

4: High Speed

Disabled

Run at High Speed (P8-06)

5: High Speed 5

Disabled

Run at High Speed 5 (P8-12)

6: Inspection Speed

Disabled

Run at Inspection Speed (P8-08)

7: Fault Reset

Disabled

Reset Fault

8: Rescue Mode

Mains Mode

Rescue Mode

9: E-Trip Mode 1

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

Ok

10: Preset with override High Speed 

Levelling Speed or Selected Speed from Setting 11 & 12

High Speed

11: Preset with override Inspection Speed

Levelling Speed or Selected Speed from Setting 10 & 12

Inspection Speed

12: Preset with override Intermediate Speed

Levelling Speed or Selected Speed from setting 10 & 11

Intermediate Speed

13: E-Trip Mode 2 

  • E-Trip when open with no other functions enabled

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

Ok

14: Preset Bit 0 (2)

Speed Selection Bit 0 Low

Speed Selection Bit 0 High

15: Preset Bit 1 (2) 

Speed Selection Bit 1 Low

Speed Selection Bit 1 High

16: Preset Bit 2 (2)

Speed Selection Bit 2 Low

Speed Selection Bit 2 High

17: Speed Reference 

Speed Reference

Speed Reference

18: Torque Sensor 

Input is used as torque feedback from external sensor

Input is used as torque feedback from external sensor

19: Forward, Contactor Control

Disabled

Close Motor Contactor & Run Forward

20: Reverse, Contactor Control

Disabled

Close Motor Contactor & Run Reverse

21: Drive Enable

Disabled

Enable Drive

22: E-Trip Mode 3

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

Ok

23: Brake Release Monitor Input 1

Brake Release Monitoring 1 Input Open

Brake Release Monitoring 1 Input Closed

24: Brake Release Monitor Input 2 

Brake Release Monitoring 2 Input Open

Brake Release Monitoring 1 Input Closed

25: Analog mode 

Analog Speed Reference

Analog Speed Reference

26: Direction (0 – Fwd, 1 - Rev)

Run Forward

Run Reverse

27: Preset Bit 0 With Active (3) 

Speed Selection Bit 0 Low (requires 1 bit High to run)

Speed Selection Bit 0 Low (requires 1 bit High to run)

28: Preset Bit 1 With Active (3)

Speed Selection Bit 1 Low (requires 1 bit High to run)

Speed Selection Bit 1 Low (requires 1 bit High to run)

29: Preset Bit 2 With Active (3)

Speed Selection Bit 2 Low (requires 1 bit High to run)

Speed Selection Bit 2 Low (requires 1 bit High to run)

When P1-02 = 0 these two parameters are used to select the Function of each digital input terminal (Daux 1 & Daux 2) on the Universal Encoder Module from the table below:

Drop Down Options

Function

Open

Closed

0: No Function

Input Disabled

Input Disabled

1: Run Forward

Disabled

Run Forward

2: Run Reverse

Disabled

Run Reverse

3: Levelling Speed

Disabled

Run at Levelling Speed (P8-05)

4: High Speed

Disabled

Run at High Speed (P8-06)

5: High Speed 5

Disabled

Run at High Speed 5 (P8-12)

6: Inspection Speed

Disabled

Run at Inspection Speed (P8-08)

7: Fault Reset

Disabled

Reset Fault

8: Rescue Mode

Mains Mode

Rescue Mode

9: E-Trip Mode 1

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

Ok

10: Preset with override High Speed 

Levelling Speed or Selected Speed from Setting 11 & 12

High Speed

11: Preset with override Inspection Speed

Levelling Speed or Selected Speed from Setting 10 & 12

Inspection Speed

12: Preset with override Intermediate Speed

Levelling Speed or Selected Speed from setting 10 & 11

Intermediate Speed

13: E-Trip Mode 2 

  • E-Trip when open with no other functions enabled

  • Motor Contactor feedback trip if P3-02 is set to 1 (Enabled)

Ok

14: Preset Bit 0 (2)

Speed Selection Bit 0 Low

Speed Selection Bit 0 High

15: Preset Bit 1 (2) 

Speed Selection Bit 1 Low

Speed Selection Bit 1 High

16: Preset Bit 2 (2)

Speed Selection Bit 2 Low

Speed Selection Bit 2 High

17: Speed Reference 

Speed Reference

Speed Reference

18: Torque Sensor 

Input is used as torque feedback from external sensor

Input is used as torque feedback from external sensor

19: Forward, Contactor Control

Disabled

Close Motor Contactor & Run Forward

20: Reverse, Contactor Control

Disabled

Close Motor Contactor & Run Reverse

21: Drive Enable

Disabled

Enable Drive

22: E-Trip Mode 3

  • E-Trip when open with no other functions enabled

  • Thermistor trip if thermistor function selected in P1-09 Analog Input 2 (DI5) Format

Ok

23: Brake Release Monitor Input 1

Brake Release Monitoring 1 Input Open

Brake Release Monitoring 1 Input Closed

24: Brake Release Monitor Input 2 

Brake Release Monitoring 2 Input Open

Brake Release Monitoring 1 Input Closed

25: Analog mode 

Analog Speed Reference

Analog Speed Reference

26: Direction (0 – Fwd, 1 - Rev)

Run Forward

Run Reverse

27: Preset Bit 0 With Active (3) 

Speed Selection Bit 0 Low (requires 1 bit High to run)

Speed Selection Bit 0 Low (requires 1 bit High to run)

28: Preset Bit 1 With Active (3)

Speed Selection Bit 1 Low (requires 1 bit High to run)

Speed Selection Bit 1 Low (requires 1 bit High to run)

29: Preset Bit 2 With Active (3)

Speed Selection Bit 2 Low (requires 1 bit High to run)

Speed Selection Bit 2 Low (requires 1 bit High to run)

Group 12.2 - User I/O Configuration - Parameter References

Parameter Number

Parameter Name

Units

Default

Available Settings

Drop Down Options

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P12-11

Speed reference source

N/A

0

0 ... 5

N/A

RO

Y

N/A

1

24BBh

0

1211

P12-12

Reference active

N/A

0

0 ... 1

N/A

RO

Y

N/A

1

24BCh

0

1212

P12-13

User pre-ramp reference 

Hz

0.00

-P8-01 to P8-01

N/A

RO

Y

1 = 0.1 Hz

2

24BDh

0

1213

Shows the active speed source reference.

Shows if a speed reference is active.

Shows the active Pre-ramp speed reference.