Group 11 Parameter Descriptions
Group 11.1 - Drive Configuration - On-board Back-up of User Parameter Settings
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-01 | Save User Defaults | N/A | 0: No Action | 0 ... 2 | RW | N | N/A | 1 | 244Dh | 0 | 1101 |
The drive can store a backup of the user parameter settings, this is useful in the event of someone inadvertently adjusting the drive operational parameters and allows for the parameter settings to be returned exactly as per the original installation.
Once the drive has been programmed for the application, setting parameter P11-01 to a 1 will save the drive parameters as user default parameters.
Settings | Function |
|---|---|
0 | No Action |
1 | Saves the current parameter settings as "User default parameters". When the User carries out a 3-button default parameter command (UP, DOWN and STOP), the parameters saved when P11-01 was last set to 1 will be restored. The display will show the message Usr-PS to indicate the values have been saved. |
2 | Clears user parameters. A 3-button default with no user default parameters saved will restore factory defaults. The display will show the message USr-cL to indicate factory defaults have now been loaded. |
Group 11.2 - Drive Configuration - Parameter Access Lock
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-02 | Extended Group Access Code | N/A | 0 | 0 ... 9999 | RW | Y | N/A | 2 | 244Eh | 0 | 1102 |
P11-03 | Parameter Access Lock | N/A | 0: Unlocked | 0: Unlocked 1: Locked | RW | Y | N/A | 1 | 244Fh | 0 | 1103 |
P11-04 | Level 2 Access Definition | N/A | 101 | 0 ... 9999 | RW | Y | N/A | 2 | 2450h | 0 | 1104 |
The value entered in parameter P11-02 determines which parameter groups are accessible by the user by default if:
P11-02 = 0 = Level 1 parameter groups can be accessed.
P11-02 = 101 = Level 2 parameter groups can be accessed.
Level 1 access includes groups 0 through to group 11.
Level 2 access includes groups 0 through to group 12.
The code for Level 2 can be changed by the user by setting the desired value into parameter P11-04.
Setting | Function |
|---|---|
0 | All parameters can be accessed and changed |
1 | Parameters are made read only (apart from P11-02 and P11-04) |
Enter your chosen access code here (> 0) which once set must be entered in P11-02 to access parameter Group 2.
Once set this parameter will become hidden until the same value is entered into P11-02.
Note
When the menu access code (P11-04) is changed then it must be retained in a safe location for further reference to allow further configuration or service. Forgotten access codes can be cleared by returning the drive back to default settings. A default is performed by pressing STOP, UP and DOWN buttons simultaneously for more than 2 seconds. This will clear all drive parameters, including the security codes back to default values.
Group 11.3 - Drive Configuration - Drive Operational Management
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-05 | Effective Switching Frequency | kHz | 8.0kHz | 2.0 ... 10.0kHz | RW | N | 1 = 0.1Hz | 1 | 2451h | 0 | 1105 |
P11-06 | Auto Thermal Management | kHz | 2.0kHz | 2.0 ... 10.0kHz | RW | N | 1 = 0.1Hz | 1 | 2452h | 0 | 1106 |
P11-07 | Thermal Overload Value Retention Enable | N/A | 0: Disabled | 0: Disabled 1: Enabled | RW | N | N/A | 1 | 2453h | 0 | 1107 |
P11-08 | Reserved | N/A | Reserved | Reserved | Reserved | - | - | - | - | - | - |
P11-09 | Output Phase Sequence | N/A | 0: U, V, W | 0: U, V, W 1: U, W, V | RW | N | N/A | 1 | 2455h | 0 | 1109 |
P11-10 | PWM Modulation Type | N/A | 0: 3-Phase | 0: 3-Phase 1: 2-Phase 2: Auto | RW | N | N/A | 1 | 2456h | 0 | 1110 |
Selects the type of PWM modulation.
Higher switching frequencies reduce the audible ‘ringing’ noise from the motor and improve the output current waveform at the expense of increased drive losses.
This parameter defines the minimum switching frequency which the drive will use when the drive auto- switches down the switching frequency (Based on Heatsink Temperature and motor current) in order to reduce the losses and heat from the power stage.
Setting | Function |
|---|---|
0 | Disabled (No retention when the drive is powered off). |
1 | Enabled (retention). An internal overload accumulator (P0-31) monitors the motor output current over time, and will trip the drive if the usage exceeds the thermal limit. |
Reserved
Select the motor phase orientation.
Setting | Orientation |
|---|---|
0 | U, V, W |
1 | U, W, V Direction of motor rotation when operating in a forward direction will be reversed |
Setting | Modulation type |
|---|---|
0 | 3-Phase |
1 | 2-Phase |
2 | Auto |
Group 11.4 - Drive Configuration - Display Scaling Source
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-11 | Display Scaling Factor | N/A | 0.000 | -30.000 ... 30.000 | RW | Y | 1 = 0.001 | 2 | 2457h | 0 | 1111 |
P11-12 | Display Scaling Source | N/A | 2 | 0 ... 6 | RW | Y | N/A | 1 | 2458h | 0 | 1112 |
If P11-11 is set >0, the variable selected in P11-12 is multiplied by the factor entered in P11-11, and displayed whilst the drive is running with a ‘c’ to indicate the customer scaled units.
P11-11 & P11-12 allow the user to program the drive to display an alternative output unit scaled from an existing parameter, e.g. to display speed in meters per second based on the output frequency.
Note
This function is disabled if P11-11 is set to 0.
Source to be multiplied by P11-11
Setting | Scaling Source |
|---|---|
0 | Motor Speed |
1 | Motor Current |
2 | Speed Error (As defined by parameter P0-16 (Speed Following Error) |
3 | Encoder Offset (Real-Time) (As per P0-20) |
4 | Elevator Sequence Segment (As per P0-35) |
5 | Rollback Error Count (As defined by P0-17) |
6 | P0-75 (signed with one decimal place) – Internal use only |
Group 11.5 - Drive Configuration - Cooling Fan Control
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-13 | Reset Cooling Fan Run-time | N/A | 0: Disabled | 0: Disabled 1: Reset | RW | N | N/A | 1 | 2459h | 0 | 1113 |
P11-14 | Cooling Fan Control | N/A | 0 | 0 ... 1 | RW | N | N/A | 1 | 245Ah | 0 | 1114 |
P11-15 | Cooling Fan Run-time After Disable | sec | 60s | 0 ... 600s | RW | N | N/A | 2 | 245Bh | 0 | 1115 |
Resets the internal fan run-time counter to zero (as displayed in P0-55).
Setting | Function |
|---|---|
0 | Disabled |
1 | Reset fan run-time counter in P0-55 |
Sets how the drive fan should operate when the turn on conditions are reached.
Setting | Function |
|---|---|
0 | The fan is controlled by the drives internal temperature measurement regardless of if drive is running or not. When P0-48 reaches 45°C then fan will turn on and stay on until the temperature drops below 40°C, as long as the drive has not run during the time the temperature reaches 45°C and then falls below 40°C. If drive runs while above 45°C then the fan will stay on until the time in P11-15 has elapsed, even if the temperature in P0-48 drops below 40°C. |
1 | The fan will only run when the drive is given a run command and the value in P0-48 is 45°C or above. |
This parameter defines the fan run time after the drive has stopped running when the temperature in P0-48 reaches 45°C.
Group 11.6 - Drive Configuration - Service Time
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-16 | Resets kWh Meter | N/A | 0: Disabled | 0: Disabled 1: Reset | RW | N | N/A | 1 | 245Ch | 0 | 1116 |
P11-17 | Service time interval | hours | 0h | 0 ... 65535h | RW | N | 1 = 1 hour | 2 | 245Dh | 0 | 1117 |
P11-18 | Time remaining to next service | hours | 0h | -65536 ... 65535h | RO | N | 1 = 1hour | 2 | 245Eh | 0 | 1118 |
P11-19 | Reset service time indicator | N/A | 0: Disabled | 0: Disabled 1: Reset | RW | Y | N/A | 1 | 245Fh | 0 | 1119 |
Setting to 1 resets the internal energy consumption kWh meter to zero (as displayed in P13-57 and P13-58).
This defines the total number of run time hours which must elapse before the Service indicator output comes on.
For example if terminal DA1 is set to Digital Output and Parameter P1-15 is set at 14: Service Indicator then once the value in this parameter has been met the Digital Output changes to Logic 1.
Note
To reset this value set P11-19 to 1.
Displays the number of hours remaining on the service counter before the next service is due
A negative value shows the service overdue hours.
When this parameter is set to 1, the internal Service time interval counter (P11-17) is reset.
Group 11.7 - Drive Configuration - Motor Thermistor Configuration
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-20 | Motor Thermistor Trip Threshold | Ω | 2500Ω | 0 ... 5000Ω | RW | Y | 1 = 1Ω | 2 | 2460h | 0 | 1120 |
P11-21 | Motor Thermistor Reset Threshold | Ω | 1900Ω | 0 ... 5000Ω | RW | Y | 1 = 1Ω | 2 | 2461h | 0 | 1121 |
Sets the trip threshold resistance for the connected motor thermistor.
Sets the trip reset threshold resistance for the connected motor thermistor.
Group 11.8 - Drive Configuration - Display Index
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-22 | P0-75 Display Index | N/A | 0 | 0 ... 99999 | RW | Y | N/A | 2 | 2462h | 0 | 1122 |
Internal Use only
Group 11.9 - Drive Configuration - Sequence Detection
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-23 | Disable Run Sequence Error Detection | N/A | 1: Disabled | 0: Disabled 1: Enabled | RW | Y | N/A | 1 | 2463h | 0 | 1123 |
P11-24 | STO Status Detection Time | sec | 2.0s | 0.0 ... 10.0s | RW | Y | N/A | 2 | 2464h | 0 | 1124 |
P11-25 | STO-L Trip Disable | N/A | 0: Enabled | 0: Enabled 1: Disabled | RW | N | N/A | 1 | 2465h | 0 | 1125 |
While enabled (setting 0) this function checks that the control commands sent from the controller to the drive are in the following expected order:
Safe Torque Off inputs given
Speed Selection given
Direction command given.
If the order differs then the drive will trip Odr-Er.
If set to 1 then this feature is disabled and the drive will not trip.
Setting | Function |
|---|---|
0 | Run Sequence Error detection Enabled |
1 | Run Sequence Error detection Disabled |
Sets the time that when the drive stops the Safety Chain inputs (STO1 and STO2) must open. If the STO inputs do not change state then the drive will trip Sto-S.
This is used to detect a short circuit of the drive STO ports.
Setting P11-24 to 0.0 will disable this function.
This parameter allows you to disable the Sto-L trip by setting the value to 1. So when both STO terminals (STO1 & STO2) are opened while the drive is running the drive will not trip By default the Sto-L trip is enabled.
It is recommended that you keep the Sto-L trip enabled to show if there is a fault with the Safe Torque Off Ports (STO1 & STO2).
Setting | Function |
|---|---|
0 | Sto-L Trip Enabled |
1 | Sto-L Trip Disabled |
Group 11.10 - Drive Configuration - Read Only Parameters
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
|---|---|---|---|---|---|---|---|---|---|---|---|
P11-30 | Drive Type Code | N/A | Drive Dependent | Drive Dependent | RO | N | N/A | 2 | 246Ah | 0 | 1130 |
P11-31 | Drive Branding Identifier | N/A | Drive Dependent | 0 ... 65535 | RO | N | N/A | 2 | 246Bh | 0 | 1131 |
P11-37 | Drive rated current | Amps | Drive Dependent | N/A | RO | N | 1 = 0.1A | 2 | 2471h | 0 | 1137 |
P11-38 | Drive rated voltage | Volts | Drive Dependent | N/A | RO | N | N/A | 2 | 2472h | 0 | 1138 |
P11-39 | Drive rated power (kW) | kW | Drive Dependent | N/A | RO | N | 1 = 0.1kW | 2 | 2473h | 0 | 1139 |
P11-40 | Drive rated power (HP) | HP | Drive Dependent | N/A | RO | N | 1 = 0.1HP | 2 | 2474h | 0 | 1140 |
P11-41 | Number of input phases | N/A | Drive Dependent | 1 ... 3 | RO | N | N/A | 1 | 2475h | 0 | 1141 |
P11-42 | Drive frame size | N/A | Drive Dependent | 1 ... 5 | RO | N | N/A | 1 | 2476h | 0 | 1142 |
P11-43 | Duty Rating | N/A | Drive Dependent | 0 ... 1 | RO | N | N/A | 1 | 2477h | 0 | 1143 |
P11-44 | IP Rating | N/A | Drive Dependent | 0 ... 66 | RO | N | N/A | 1 | 2478h | 0 | 1144 |