I/O Logic Select - Inputs

The Drive offers the possibility to operate the Digital Inputs in either PNP (Positive Logic) or NPN (Negative Logic).

I/O Logic Select Inputs - Setup Process

Below is the setup process for selecting the logic of the Digital Inputs.

  1. Decide which configuration of logic you will be using. The default is positive logic (P1-43 = 0)

  2. While the drive is powered off make the necessary wiring adjustments so that your I/O wiring matches your logic selection.

  3. Set P1-43 to the relevant value.

    Setting

    Logic

    0

    Positive Logic

    1

    Negative Logic

  4. Power on the drive.

    Caution

    When powering on the drive after switching logic always make sure the Safe Torque Off inputs are not closed so the drive can not start. Incorrect wiring/parameter settings could cause the car start start unintentionally.

  5. Check P0-01 and P0-02 to make sure that your Digital Inputs are in the correct state and are changing state properly.

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P0-01

Digital Input 1 to 5 Status

N/A

0

0 ... 31

RO

N

N/A

1

2012h

0

10001

P0-02

Digital Input 6 to 10 Status

N/A

0

0 ... 31

RO

N

N/A

1

2012h

0

10002

P1-43

Positive/Negative Logic Select

N/A

0: Positive Logic

0: Positive Logic

1: Negative Logic

RW

N

N/A

1

208Fh

0

143

Changes the control logic for all Digital Inputs (including the Universal Encoder module terminals Daux1 and Daux2).

Setting

Logic

0

Positive Logic

1

Negative Logic

Note

STO1 and STO2 Inputs are always positive logic.