Group 7.1 Rescue Operation - Rescue Mode Setup

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P7-01

Rescue Supply type

N/A

0: 230V UPS

0: 230V UPS

1: 400V UPS

2: Battery Operation

RW

N

N/A

1

22BDh

0

701

P7-02

Rescue Operation Function

N/A

0: Basic Rescue Mode

0: Basic Rescue Mode

1: Light Load Detection

2: UPS Easiest Direction based on Load Measurement

3: Energy Optimized

RW

N

N/A

1

22BEh

0

702

Select what type of power supply is being used for Rescue Mode Operation.

Setting

Power Supply

UPS230

230VAC 1ph UPS

UPS400

400VAC 2ph UPS

bAtt

Battery Operation

Setting

Function

0

Basic Rescue Mode

1

Light Load Detection

2

UPS Easiest Direction based on Load Measurement

3

Energy Optimized

There are 3 types of rescue mode operation, the following points of consideration help select the most suitable mode:

  • If the controller is to choose the direction of travel, then mode 0 should be used.

  • Mode 1 and 2 lets the drive measure which is the easiest direction of travel to consume the least amount of energy from the UPS/Battery. Mode 1 selects while in Rescue Operation, Mode 2 selects while in normal operation.

  • Mode 3 is when the drive output should be switched off and controlled by the motor brake.