Group 7.1 Rescue Operation - Rescue Mode Setup
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-01 | Rescue Supply type | N/A | 0: 230V UPS | 0: 230V UPS 1: 400V UPS 2: Battery Operation | RW | N | N/A | 1 | 22BDh | 0 | 701 |
P7-02 | Rescue Operation Function | N/A | 0: Basic Rescue Mode | 0: Basic Rescue Mode 1: Light Load Detection 2: UPS Easiest Direction based on Load Measurement 3: Energy Optimized | RW | N | N/A | 1 | 22BEh | 0 | 702 |
Select what type of power supply is being used for Rescue Mode Operation.
Setting | Power Supply |
---|---|
UPS230 | 230VAC 1ph UPS |
UPS400 | 400VAC 2ph UPS |
bAtt | Battery Operation |
Setting | Function |
---|---|
0 | Basic Rescue Mode |
1 | Light Load Detection |
2 | UPS Easiest Direction based on Load Measurement |
3 | Energy Optimized |
There are 3 types of rescue mode operation, the following points of consideration help select the most suitable mode:
If the controller is to choose the direction of travel, then mode 0 should be used.
Mode 1 and 2 lets the drive measure which is the easiest direction of travel to consume the least amount of energy from the UPS/Battery. Mode 1 selects while in Rescue Operation, Mode 2 selects while in normal operation.
Mode 3 is when the drive output should be switched off and controlled by the motor brake.