Elevator Core CANopen Drive Control Word Format

Table 15. Control Word Bit and Byte Format

Bit Number

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Byte

High Byte

Low Byte



Bit 0: Run Forward / Stop command: Set to 1 to enable the drive and run forward. Set to 0 to stop the drive.

Bit 1: Run Reverse / Stop command: Set to 1 to enable the drive and run reverse. Set to 0 to stop the drive.

Bit 2: Reset request. Set to 1 in order to reset the drive if drive is under trip condition.

User must clear this bit when drive is under normal condition to prevent un-expected reset.

Important

Drive must be set to CANopen command source in P1-01 to run the drive via CANopen.

To run the drive using the Control Word the following conditions must be fulfilled:

  • The Safety Chain is closed (STO1 and STO2 are closed)

  • P1-01 must be set to 2 : CANopen

  • The drive must not be in a tripped state

  • All commissioning steps are completed

Frequency Setpoint value is transferred with one decimal place (500 = 50.00Hz). The maximum value is limited by P8-01. Sending a value that exceeds P8-01 will result in an Exception error.