Group 10.6 Extended Functions - Anti-Stall
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P10-09 | Anti-Stall Enable | N/A | 0: Disabled | 0: Disabled 1: Enabled | RW | N | N/A | 1 | 23F1h | 0 | 1009 |
P10-10 | Anti-Stall Limit | % | 100.0% | 100.0 ... 250.0% | RW | N | 1 = 0.1 % | 2 | 23F2h | 0 | 1010 |
P10-11 | Anti-Stall Hysteresis | % | 10.0% | 0.0 ... 50.0% | RW | N | 1 = 0.1 % | 2 | 23F3h | 0 | 1011 |
Setting | Function |
---|---|
0 | No Anti-Stall Prevention, if the acceleration time is too short for a given high load, then the drive can trip on over-current. |
1 | Anti-Stall Prevention enabled: If During acceleration the output current exceeds the value set in the Anti-stall limit parameter P10-10 then the drive will stop accelerating and hold the current speed, once the current drops below the value set in P10-10 minus the Anti-Stall hysteresis band P10-11 then acceleration will continue. |
Set as a % of motor rated current
Set as a % of motor rated current
The value set should be below the value set in the torque limit parameters P4-18 and P4-19 so that the 2 functions don’t conflict with each other.