Group 7 Rescue Operation - Parameter List
Group 7.1 Rescue Operation - Rescue Mode Setup
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-01 | Rescue Supply type | N/A | 0: 230V UPS | 0: 230V UPS 1: 400V UPS 2: Battery Operation | RW | N | N/A | 1 | 22BDh | 0 | 701 |
P7-02 | Rescue Operation Function | N/A | 0: Basic Rescue Mode | 0: Basic Rescue Mode 1: Light Load Detection 2: UPS Easiest Direction based on Load Measurement 3: Energy Optimized | RW | N | N/A | 1 | 22BEh | 0 | 702 |
Group 7.2 Rescue Operation - Basic Rescue Mode
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-03 | Rescue Mode Speed | Hz / rpm / ft/s / m/s | 5.00Hz | P8-02 ... P8-01 | RW | Y *Does not take effect until next travel | 1 = 0.1 Hz | 2 | 22BFh | 0 | 703 |
Group 7.3 Rescue Operation - UPS Protection Function
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-04 | UPS Rating | kW | 0.0 | 0.0 ... 65535 | RW | Y | 1 = 0.1 kW | 2 | 22C0h | 0 | 704 |
P7-05 | Rescue Mode Current Limit | % | 100.0% | 0.0 ... 200.0% | RW | Y | 1 = 0.1% | 2 | 22C1h | 0 | 705 |
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-06 | Rescue Mode Proportional Speed Loop Gain | % | 10.0% | 0.0 ... 400.0% | RW | Y | 1 = 0.1% | 2 | 22C2h | 0 | 706 |
P7-07 | Rescue Mode Integral Speed Loop Gain | ms | 50ms | 0 ... 1000ms | RW | Y | 1 = 0.1ms | 2 | 22C3h | 0 | 707 |
Group 7.4 Rescue Operation - Light Load Detection
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-08 | Light Load Detection Measurement time | sec | 1.0s | 0.0 ... 10.0s | RW | Y | 1 = 0.1s | 1 | 22C4h | 0 | 708 |
P7-09 | Light Load Detection Speed | Hz / rpm / ft/s / m/s | 5.00 | P8-02 ... P8-01 | RW | Y *Does not take effect until next travel | 1 = 0.01Hz 1 = 1rpm | 2 | 22C5h | 0 | 709 |
Group 7.5 Rescue Operation - UPS Easiest Direction based on Load Measurement
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-10 | Load Measurement extended time | sec | 0.0s | 0.0 ... 10.0s | RW | Y | 1 = 0.1s | 1 | 22C6h | 0 | 710 |
P7-11 | Light Load Detection Results | N/A | 0: Light direction is clockwise | 0: Light direction is clockwise 1: Light direction is Anti-clockwise 2: Balanced | RO | N | N/A | 1 | 22C7h | 0 | 711 |
Group 7.6 Rescue Operation - Energy Optimisation
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-12 | Energy Saving Rescue Unbalancing Max speed | Hz / rpm / ft/s / m/s | 5.00 Hz | P8-02 ... P8-01 | RW | Y | 1 = 0.01Hz | 2 | 22C8h | 0 | 712 |
P7-13 | Energy Saving Rescue Minimum Speed | Hz / rpm / ft/s / m/s | 5.00 Hz | P8-02 ... P8-01 | RW | Y | 1 = 0.01Hz | 2 | 22C9h | 0 | 713 |
P7-14 | Energy Saving Rescue Minimum Speed Time | sec | 0.0s | 0.0 ...10.0s | RW | Y | 1 = 0.1s | 1 | 22CAh | 0 | 714 |
Group 7.8 - Rescue Mode Read Only
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-15 | Rescue mode active | N/A | 0: Mains Supply | 0: Mains Supply 1: Rescue Supply | RO | N | N/A | 1 | 22CBh | 0 | 715 |
Group 7.9 - Rescue Mode UPS Limit
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P7-16 | UPS overload time limit | sec | 2.0s | 0.0 ... 10.0s | RW | N | 1 = 0.1s | 1 | 22CCh | 0 | 716 |