Skip to main content

Elevator Core Reference Guide

Group 11.3

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P11-05

Effective Switching Frequency

kHz

8.0 kHz

2.0 ... 10.0 kHz

RW

N

1 = 0.1 Hz

1

2451h

0

1105

P11-06

Auto Thermal Management

kHz

2.0 kHz

2.0 ... 10.0 kHz

RW

N

1 = 0.1 Hz

1

2452h

0

1106

P11-07

Thermal Overload Value Retention Enable

N/A

0: Disabled

0: Disabled

1: Enabled

RW

N

N/A

1

2453h

0

1107

P11-08

Reserved

N/A

Reserved

Reserved

Reserved

-

-

-

-

-

-

P11-09

Output Phase Sequence

N/A

0: U, V, W

0: U, V, W

1: U, W, V

RW

N

N/A

1

2455h

0

1109

P11-10

PWM Modulation Type

N/A

0: 3-Phase

0: 3-Phase

1: 2-Phase

2: Auto

RW

N

N/A

1

2456h

0

1110

IGBT Switching Frequency.

Selects the type of PWM modulation.

Higher switching frequencies reduce the audible ‘ringing’ noise from the motor and improve the output current waveform at the expense of increased drive losses.

This parameter defines the minimum effective switching frequency which the drive will use when the drive auto- switches down the switching frequency (Based on Heatsink Temperature and motor current) in order to reduce the losses and heat from the power stage.

When P11-07 is 0, removing the power supply from the drive and re-applying will reset the value of the accumulator.

When P11-07 is 1, the value is retained during power off.

Setting

Function

0

Disabled (No retention)

1

Enabled (retention). An internal overload accumulator (P0-31) monitors the motor output current over time, and will trip the drive if the usage exceeds the thermal limit.

Select the motor phase orientation.

Setting

Orientation

0

U, V, W

1

U, W, V Direction of motor rotation when operating in a forward direction will be reversed

Setting

Modulation type

0

3-Phase

1

2-Phase

2

Auto