UPS Easiest Direction based on Measurement

UPS Easiest Direction is a operation mode that is available when the drive is in Rescue Mode (P7-15 = 1).

To select UPS Easiest Direction set P7-02 = 2.

The function measures which direction is the easiest direction to run in during the start of each run while in mains mode. The result is then stored in P7-11 so when Rescue Mode is activated no test is needed to find the easiest direction to run in.

The results in P7-11 are as follows:

P7-11 Result

Function

0

Forward - Up (clockwise facing sheave)

1

Reverse- Down (anti-clockwise facing sheave)

2

Balanced - Switch Rescue Operation function mode

While in Rescue Mode once a direction command is given and the run conditions are fulfilled the drive will follow the direction stored in P7-11, similar to Basic Rescue Mode (P7-02 = 0) no matter which direction command was given.

The image below shows how the timing of the function works and when switching from Mains Mode to Rescue Mode.

Rescue_Mode_-_Functions_-_Easiest_Direction_Measurement.svg

To setup the function follow the steps:

  1. Set P7-02 = 2 to enable UPS Easiest Direction function.

  2. Set the measurement time using P5-01 for the initial measurement then P7-10 if extra time needed. A total of 15 seconds is available (5 seconds in P5-01 and 10 seconds in P7-10).

  3. While in MAINS MODE (P7-15 = 0) run the drive as normal.

  4. Once the drive has stopped P7-11 automatically stores the result.

  5. When next switching to Rescue Mode (P7-15 =1), if the drive is given a run command the direction stored by P7-11 will be the running direction for travel.

Important

If a balanced scenario occurs (P7-11 = 2), the drive will automatically switch to a different function of P7-02 depending on the motor control mode selected in P4-01.

The balanced scenarios for each motor type are:

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P7-02

Rescue Operation Function

N/A

0: Basic Rescue Mode

0: Basic Rescue Mode

1: Light Load Detection

2: UPS Easiest Direction based on Load Measurement

3: Energy Optimized

RW

N

N/A

1

22BEh

0

702

P7-10

Load Measurement extended time

sec

0.0s

0.0 ... 10.0s

RW

Y

1 = 0.1s

1

22C6h

0

710

P7-11

Light Load Detection Results

N/A

0: Light direction is clockwise

0: Light direction is clockwise

1: Light direction is Anti-clockwise

2: Balanced

RO

N

N/A

1

22C7h

0

711

Setting

Function

0

Basic Rescue Mode

1

Light Load Detection

2

UPS Easiest Direction based on Load Measurement

3

Energy Optimized

There are 3 types of rescue mode operation, the following points of consideration help select the most suitable mode:

  • If the controller is to choose the direction of travel, then mode 0 should be used.

  • Mode 1 and 2 lets the drive measure which is the easiest direction of travel to consume the least amount of energy from the UPS/Battery. Mode 1 selects while in Rescue Operation, Mode 2 selects while in normal operation.

  • Mode 3 is when the drive output should be switched off and controlled by the motor brake.

Sets the extended measurement time which starts of P5-01 has finished.

Increasing this value can help improve the measurement accuracy of the feature.

Shows the result of either the Light Load Detection Test (P7-02 = 1) or the UPS Easiest direction based on measurement result (P7-02 = 2).

Value

Result

0

Light direction is clockwise

1

Light direction is Anti-clockwise

2

Balanced