Group 10.2 Extended Functions - Early Door Opening

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P10-02

Early Door Opening Speed Threshold

%

0.0%

0.0 ... 100.0%

RW

Y

1 = 0.1 %

2

23EAh

0

1002

Any of the drives digital outputs or relays can be set to give an output when the door zone speed condition has been met (setting 16), example of using Digital output 3 shown above.

The output will only come on during deceleration approaching the floor.

The Early Door opening function is used to provide the elevator controller with a signal (From a digital output) at a set speed to open the elevator doors prior to reaching the exact floor level (saving time at stop to open the doors).