Group 7.5 Rescue Operation - UPS Easiest Direction based on Load Measurement

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P7-10

Load Measurement extended time

sec

0.0s

0.0 ... 10.0s

RW

Y

1 = 0.1s

1

22C6h

0

710

P7-11

Light Load Detection Results

N/A

0: Light direction is clockwise

0: Light direction is clockwise

1: Light direction is Anti-clockwise

2: Balanced

RO

N

N/A

1

22C7h

0

711

Sets the extended measurement time which starts of P5-01 has finished.

Increasing this value can help improve the measurement accuracy of the feature.

Shows the result of either the Light Load Detection Test (P7-02 = 1) or the UPS Easiest direction based on measurement result (P7-02 = 2).

Value

Result

0

Light direction is clockwise

1

Light direction is Anti-clockwise

2

Balanced