Group 1 User IO - Parameter List

Group 1.1 User IO - Primary Command Source Selection

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-01

Primary Command Source

N/A

0: Terminal

0: Terminal

1: Modbus RTU

2: CANopen

3: Reserved

RW

N

N/A

1

2065h

0

101

Group 1.2 User IO - Control Terminal Function Select

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-02

Control Terminal Function Select

N/A

1: Macro 1

0: Macro 0

1: Macro 1

2: Macro 2

3: Macro 3

4: Macro 4

5: Macro 5

6: Macro 6

7: Macro 7

8: Macro 8

9: Macro 9

10: Macro 10

11: Macro 11

12: Macro 12

RW

N

N/A

1

2066h

0

102

Group 1.3 User IO - Analog Input 1 (DI4) configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-03

DI4 Analog Input 1 Format

N/A

0: U 0-10

See Table

RW

N

N/A

1

2067h

0

103

P1-04

DI4 Analog Input 1 Offset

%

0.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

2068h

0

104

P1-05

DI4 Analog Input 1 Scaling

%

100.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

2069h

0

105

P1-06

DI4 Analog Input 1 Filter

sec

0.00s

0.00 ... 2.00 s

RW

Y

1 = 0.01 s

1

206Ah

0

106

P1-07

DI4 Analog Input Signal Loss Reaction

N/A

0: No Reaction

0 ... 2

RW

Y

N/A

1

206Bh

0

107

P1-08

DI4/DI5 Analog Input Signal Loss Speed

%

80.00%

0.00 ... 100.00 %

RW

Y

1 = 0.01%

1

206Ch

0

108

Group 1.4 User IO - Analog Input 2 (DI5) configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-09

DI5 Analog Input 2 Format

N/A

0: U 0-10

0 ... 9

RW

Y

N/A

1

206Dh

0

109

P1-10

DI5 Analog Input 2 Offset

%

0.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

206Eh

0

110

P1-11

DI5 Analog Input 2 Scaling

%

100.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

206Fh

0

111

P1-12

DI5 Analog Input 2 Filter

sec

0.00s

0.00 ... 2.00 s

RW

Y

1 = 0.01 s

1

2070h

0

112

P1-13

DI5 Analog Input 2 Signal Loss Reaction

N/A

0: No Reaction

0 ... 2

RW

Y

N/A

1

2071h

0

113

Group 1.5 User IO - DA1 Output 1 configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-14

DA1 Output 1 Type

N/A

0: Digital Output

0 ... 1

RW

Y

N/A

1

2072h

0

114

P1-15

DA1 Digital Output 1 Function Select

N/A

1: Drive Healthy

0 ... 20

RW

Y

N/A

1

2073h

0

115

P1-16

DA1 Digital Output 1 Invert

N/A

0: Standard

0: Standard

1: Inverted

RW

Y

N/A

1

2074h

0

116

P1-17

DA1 Analog Output 1 Source Select

N/A

0 : Output Frequency

0 ... 5

RW

Y

N/A

1

2075h

0

117

P1-18

DA1 Analog Output 1 Format

N/A

0: U 0-10

0 ... 5

RW

Y

N/A

1

2076h

0

118

P1-19

DA1 Analog Output 1 Scaling

%

100.0%

0.0 ... 500.0 %

RW

Y

1 = 0.1%

1

2077h

0

119

P1-20

DA1 Analog Output 1 Offset

%

0.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

2078h

0

120

Group 1.6 User IO - DA2 Output 2 configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-21

DA2 Output 2 Type

N/A

0: Digital Output

0 ... 1

RW

Y

N/A

1

2079h

0

121

P1-22

DA2 Digital Output 2 Function Select

N/A

0: Drive Enabled (Running)

0 ... 20

RW

Y

N/A

1

207Ah

0

122

P1-23

DA2 Digital Output 2 Invert

N/A

0: Standard

0: Standard

1: Inverted

RW

Y

N/A

1

207Bh

0

123

P1-24

DA2 Analog Output 2 Source Select

N/A

0: Output Frequency

0 ... 5

RW

Y

N/A

1

207Ch

0

124

P1-25

DA2 Analog Output 2 Format

N/A

0: U 0-10

0 ... 5

RW

Y

N/A

1

207Dh

0

125

P1-26

DA2 Analog Output 2 Scaling

%

100.0%

0.0 ... 500.0 %

RW

Y

1 = 0.1%

2

207Eh

0

126

P1-27

DA2 Analog Output 2 Offset

%

0.0%

-500.0 ... 500.0 %

RW

Y

1 = 0.1%

2

207Fh

0

127

Group 1.7 User IO - Digital Output 3 Configuration

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-28

DO3 Digital Output 3 Function Select

N/A

12: Motor Shorting Contactor

0 ... 20

RW

Y

N/A

1

2080h

0

128

P1-29

DO3 Digital Output 3 Invert

N/A

0: Standard

0: Standard

1: Inverted

RW

Y

N/A

1

2081h

0

129

Group 1.8 User IO - User Relays

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-30

Relay 1 Function Select

N/A

11: Motor Contactor Control

0 ... 20

RW

Y

N/A

1

2082h

0

130

Group 1.9 User IO - Hysteresis

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-31

DA1 Threshold Upper Limit

%

100.0%

P1-32 ... 200.0 %

RW

Y

1 = 0.1%

1

2083h

0

131

P1-32

DA1 Threshold Lower Limit

%

0.0%

0.0 ... P1-31

RW

Y

1 = 0.1%

1

2084h

0

132

P1-33

DA2 Threshold Upper Limit

%

100.0%

P1-34 ... 200.0 %

RW

Y

1 = 0.1%

1

2085h

0

133

P1-34

DA2 Threshold Lower Limit

%

0.0%

0.0 ... P1-33

RW

Y

1 = 0.1%

1

2086h

0

134

P1-35

Relay 1 Threshold Upper Limit

%

100.0%

0.0 ... 200.0 %

RW

Y

1 = 0.1%

1

2087h

0

135

P1-36

Relay 1 Threshold Lower Limit

%

0.0%

0.0 ... 100.0 %

RW

Y

1 = 0.1%

1

2088h

0

136

P1-37

Digital/Relay Output Hysteresis Band

%

0.3%

0.0 ... 25.0 %

RW

Y

1 = 0.1%

1

2089h

0

137

P1-38

DO3 Threshold Upper Limit

%

100.0%

0.0 ... 200.0 %

RW

Y

1 = 0.1%

1

208Ah

0

138

P1-39

DO3 Threshold Lower Limit

%

0.0%

0.0 ... 100.0 %

RW

Y

1 = 0.1%

1

208Bh

0

139

1.9 Logic Control

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P1-40

Start Mode Select / Automatic Restart

N/A

0: Edge-r

0 ... 6

RW

Y

N/A

1

208Ch

0

140

P1-41

Auto-reset delay time

sec

20s

1 ... 60s

RW

Y

N/A

1

208Dh

0

141

P1-42

Speed Following Error

%

5.0%

0.0 ... 50.0%

RW

Y

1 = 0.1%

2

208Eh

0

142

P1-43

Positive/Negative Logic Select

N/A

0: Positive Logic

0: Positive Logic

1: Negative Logic

RW

N

N/A

1

208Fh

0

143