Elevator Core Reference Guide

Group 7.3 Rescue Operation - UPS Protection Function

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P7-04

UPS Rating

kW

0.0

0.0 ... 65535

RW

Y

1 = 0.1 kW

2

22C0h

0

704

P7-05

Rescue Mode Current Limit

%

100.0%

0.0 ... 200.0%

RW

Y

1 = 0.1%

2

22C1h

0

705

Used to protect overloading/ collapsing of voltage of the UPS power supply which could cause a motor stall condition.

When the output power to the motor exceeds this value for the time set in parameter (P7-16) UPS Overload Time Limit, the drive will ramp down to Stop, apply brakes (if controlled by the drive) and trip on “UPS-L”, to restart a new direction command will need to be provided by the controller.

If value is set to 0.0 then this function is disabled.

Sets the current limit during rescue mode operation. If the drive current exceeds this value then the speed will be reduced until the current level falls below this value.