Group 2.6 Communications - Modbus Drive Monitoring

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P2-50

Modbus Control Word

N/A

0

0 ... 7

RO

N

N/A

1

20FAh

0

250

P2-51

Modbus Speed Reference

Hz

0.00

-P8-01 ... P8-01

RO

Y

N/A

2

20FBh

0

251

P2-52

Modbus Torque Reference

%

0.0

0.0 ... 100.0%

RO

Y

1 = 0.1%

2

20FCh

0

252

P2-53

Modbus Ramp Rate

sec

0.0

0.0 ... 600.0

RO

Y

1 - 0.1 s

2

20FDh

0

253

P2-56

Modbus status word lower byte: Drive status

N/A

0

0 ... 255

RO

N

N/A

2

2100h

0

256

P2-56 (1)

Modbus status word upper byte: Error code

N/A

0

0 ... 255

RO

N

N/A

2

2100h

1

256

P2-57

Modbus Speed Feedback

Hz / rpm / ft/s / m/s

0.00

-P8-01 ... P8-01

RO

N

1 = 0.1Hz

2

2101h

0

257

P2-58

Modbus Motor Current

Amps

0.0A

-3276.7 ... 3276.7A

RO

N

1 = 0.1A

2

2102h

0

258

P2-59

Modbus Output Torque

%

0.0%

-200.0 ... 200.0%

RO

N

1 = 0.1%

2

2103h

0

259

Allows the user to monitor the Control word individual bits

The drive Control Word is as follows:

Bit

Function when Bit = 0

Function When Bit = 1

0

No Function

Drive Run Forward

1

No Function

Drive Run Reverse

2

No Function

Reset Fault

Displays the speed reference received via Modbus.

Displays the torque reference received via Modbus

Displays the ramp rate received via Modbus.

Shows the real-time Modbus status word lower byte.

The below table shows the lower bytes individual bits

Bit

Function when Bit = 0

Function When Bit = 1

0

Drive Stopped

Drive Running

1

Drive Healthy

Drive Tripped

2

STO Closed

STO Open (Drive Inhibited)

3

Service Time not Reached

Service Time Reached

4

Drive not in Standby

Drive in Standby

5

Reserved

Reserved

6

Reserved

Reserved

7

Active Trip Code

Shows the real-time Modbus status word upper byte.