Group 11.5 - Cooling Fan Control
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P11-13 | Reset Cooling Fan Run-time | N/A | 0: Disabled | 0: Disabled 1: Reset | RW | N | N/A | 1 | 2459h | 0 | 1113 |
P11-14 | Cooling Fan Control | N/A | 0 | 0 ... 1 | RW | N | N/A | 1 | 245Ah | 0 | 1114 |
P11-15 | Cooling Fan Run-time After Disable | sec | 60 s | 0 ... 600 s | RW | N | N/A | 2 | 245Bh | 0 | 1115 |
Resets the internal Fan run-time counter to zero (as displayed in P0-55).
Setting | Function |
---|---|
0 | Disabled |
1 | Reset fan run-time counter in P0-55 |
Sets how the drive fan should operate when the turn on conditions are reached.
Setting | Function |
---|---|
0 | Fan controlled by internal temperature measurement regardless of if drive is running or not and P11-15 has no effect. When P0-48 reaches 45°C then fan will turn on and stay on until the temperature drops below 40°C. |
1 | Fan only runs for for time set in P11-15 only when P0-48 is above 45°C. |
This parameter defines the fan run time after the drive has stopped running when the temperature in P0-48 reaches 45°C.