Group 11.5 - Cooling Fan Control

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P11-13

Reset Cooling Fan Run-time

N/A

0: Disabled

0: Disabled

1: Reset

RW

N

N/A

1

2459h

0

1113

P11-14

Cooling Fan Control

N/A

0

0 ... 1

RW

N

N/A

1

245Ah

0

1114

P11-15

Cooling Fan Run-time After Disable

sec

60 s

0 ... 600 s

RW

N

N/A

2

245Bh

0

1115

Resets the internal Fan run-time counter to zero (as displayed in P0-55).

Setting

Function

0

Disabled

1

Reset fan run-time counter in P0-55

Sets how the drive fan should operate when the turn on conditions are reached.

Setting

Function

0

Fan controlled by internal temperature measurement regardless of if drive is running or not and P11-15 has no effect. When P0-48 reaches 45°C then fan will turn on and stay on until the temperature drops below 40°C.

1

Fan only runs for for time set in P11-15 only when P0-48 is above 45°C.

This parameter defines the fan run time after the drive has stopped running when the temperature in P0-48 reaches 45°C.