Group 3.3 System - Brake Resistor Protection

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P3-04

Brake Resistor Resistance

ohms

Rating Dependent

0 ... 60000 ohms

RW

Y

N/A

2

2130h

0

304

P3-05

Brake Resistor Power

kW

0.0kW

0.0 ... 6000.0 kW

RW

Y

1 = 1 W 

2

2131h

0

305

P3-06

Brake Resistor Temperature Monitor Enable

N/A

0: Disabled

0: Disabled

1: Enabled

RW

Y

N/A

1

2132h

0

306

P3-07

Brake Resistor Temperature Monitoring trip reaction

N/A

0 : Normal Stop, Trip After stopping

0: Normal Stop, Trip After stopping

1 : Immediate Trip, Apply motor Brake

2: Warning Only No Trip

RW

Y

N/A

1

2133h

0

307

Enter external Brake Resistor resistance in ohms.

For software protection of the connected brake resistor, enter the rated power and resistance of the resistor into the relevant parameters. The drive will then monitor the brake resistor to ensure that it does not operate outside of its designed limits. Where an external thermal protection device is fitted, and software protection is not required. Setting parameter P3-05 to zero will disable the software protection feature.

This parameter is used when a brake resistor thermal switch is wired back to a digital input set for External trip and tells the drive that the drive should trip on a brake resistor feedback fault (Ot-br) rather than an external trip.

This parameter defines the drive’s reaction when the Brake resistor overload function has been triggered (Ot-br)

Setting

Function

Reaction Details

0

Stop then Trip

Drive stops normally then trips

1

Trip Immediately

Immediate trip, apply motor brake

2

Warning Only

Warning only, no trip.