Group 9.3 Comfort Optimisation - DC Injection operation to solve rollback during starting
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P9-11 | DC Injection Time At Start | sec | 0.5s | 0.0 ... 10.0s | RW | Y | 1 = 0.1 s | 1 | 238Fh | 0 | 911 |
P9-12 | DC Injection Current At Start | % | 50% | 0.0 ... 200.0% | RW | Y | 1 = 0.1 % | 2 | 2390h | 0 | 912 |
The drive injects DC current into the motor for the time set in this parameter at the start of the travel sequence at 0.
Function Disabled if value entered = 0.0.
Best value is the shortest time but with the least amount of rollback. Also note that while DC Injection is active the speed error detection is turned off.
Sets the level of current injected into the drive for the time set in P9-11.
Value is set as a % of P4-06 motor rated current.