Group 4.3 Motor Setup - Using a Motor Thermistor for overload protection
Parameter Number | Parameter Name | Units | Default | Available Settings | Access | Change During Run | Scaling | Size (Bytes) | CAN Register | CAN Sub Index | Modbus Register |
---|---|---|---|---|---|---|---|---|---|---|---|
P4-22 | Reserved | - | - | - | - | - | - | - | - | - | - |
P4-23 | Motor Thermistor Trip Reaction | N/A | 0: Stop at Next stop command and show thermistor fault message | 0 ... 2 | RW | Y | N/A | 1 | 21A7h | 0 | 423 |
Used to set the trip reaction when a motor thermistor fault occurs.
Setting | Reaction |
---|---|
0 | Stop at Next stop command and show thermistor fault message tC-tH or ty-th depending on P1-07 or P1-13 setting. |
1 | Trip Immediately and show thermistor fault message tC-tH or ty-th depending on P1-07 or P1-13 setting. |
2 | Continue running and show thermistor fault message tC-tH or ty-th depending on P1-07 or P1-13 setting. |