Group 10.7 Extended Functions - Motor Overspeed governor Test

Parameter Number

Parameter Name

Units

Default

Available Settings

Access

Change During Run

Scaling

Size (Bytes)

CAN Register

CAN Sub Index

Modbus Register

P10-12

Overspeed Governor test speed

%

0.0%

0.0 ... 125%

RW

-

-

2

23F4h

0

1012

Parameter P10-12 can be used for testing of overspeed governors, normally performed during initial installation or scheduled inspections.

Once a value of >0.0 has been entered, the next run command from the controller to the drive will result in the motor running at the value set in terms of a % of the value set in the High-Speed parameter (P8-06), then at the next stop command the value of the parameter will return to 0.0 automatically so that the test is not repeated, and normal operation is resumed.